Mitsubishi Electric City Multi PQHY-P72 Service Handbook page 143

Mitsubishi electric air conditioners city multi service handbook
Table of Contents

Advertisement

[ VII Control ]
-8- Heat Source Unit Heat Exchanger Capacity Control <PQRY>
(1) Control method
Heat exchanger capacity is controlled by the solenoid valve (SV4a-4d,7a-7c) to keep constant the evaporating temper-
ature (0°C[32°F]=0.71MPa[103psi]) during cooling operation and condensing temperature
(49°C[120°F]=2.88MPa[418psi]) during heating operation.
(2) Heat exchanger capacity control patterns
Operation
mode
SV4a
Cooling
ON
only
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Cooling
ON
main
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Solenoid valve
SV4b
SV4c
SV4d
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
- 134 -
SV7a
SV7b
SV7c
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents