[ VIII Test Run Mode ]
(2) Heating only operation
Operation
Power supply
Ambient
tempera-
Indoor
ture
Heat source unit water tempera-
ture
Heat source unit water-flow rate
No. of connected
units
Operat-
Indoor
ing condi-
No. of units in opera-
unit
tions
tion
Model
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Heat
source
Voltage
unit
Compressor frequency
Indoor unit
LEV
opening
SC (LEV1)
High pressure/low pressure
Pressure
BC controller on the liquid side/
Intermediate part
Discharge
(TH11)
Accumu-
Heat
lator
source
unit
Temp. of
Compressor inlet
each sec-
tion
Compressor shell
bottom
LEV inlet
Indoor
Heat exchanger
unit
outlet
PQRY-P72TGMU-A
CMB-P104NU-G
V
DB/
WB
°F
°F
G/h
Unit
-
27
Ft
-
lbs-
oz
A
V
Hz
450
Pulse
psi
Inlet
Outlet
°F
- 176 -
Heat source unit model
208/230
70/-
70
1204
4
4
24
18
06
36
16
32
147
Hi
25-14
16.7/15.1
208/230
52
695
555
310
555
110/ - /520
409/116
395/395
162
32
32
34
77
100
140
PQRY-P96TGMU-A
CMB-P104NU-G
208/230
70/-
70
1521
4
4
27
24
06
16
32
147
Hi
29-6
21.0/19.0
208/230
62
450
695
310
110/ - /590
393/116
379/379
163
30
30
32
77
95
140