Mitsubishi Electric City Multi PQHY-P72 Service Handbook page 154

Mitsubishi electric air conditioners city multi service handbook
Table of Contents

Advertisement

2. Operations in each mode <PQHY>
(1) Cooling operation
1. Inverter output 0Hz
2. Indoor unit LEV,
LEV1 rated opening
3. All solenoid valves OFF
4. 52C OFF
*Note 1. The indoor fan operates at the preset speed under cooling mode regardless of the ON/OFF state of the thermostat.
Cooling operation
4-way valve OFF
Indoor unit fan
*Note 1
operation
YES
Test run mode
ON
NO
NO
Thermostat ON
YES
YES
3-minute restart
prevention
NO
1. Inverter frequency control
2. Indoor unit LEV, LEV1
rated opening
3. Solenoid valve control
4. 52C control
- 145 -
[ VII Control ]
Normal operation
During test run mode
Unit in the stopped state

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents