(3) Dry operation
1. Indoor unit fan stop
2. Inverter output 0Hz
3. Indoor LEV, LEV1 Fully closed
4. Solenoid valve OFF
5. 52C OFF
*Note 1. When the indoor unit inlet temperature exceeds 18 C [64 F], the heat source unit (compressor) and the indoor unit fan
start the intermittent operation simultaneously. When the indoor unit inlet temperature becomes 18 C [64 F] or less,
the fan always runs (at low speed). The heat source unit, the indoor unit, and the solenoid valve operate in the same
way as they do in the cooling operation when the compressor is turned on.
*Note 2. Thermostat is always kept on during test run mode, and indoor and heat source unit intermittent operation (ON) time
is a little longer than that of normal operation.
Dry operation
4-way valve OFF
YES
Test run mode
ON
NO
Thermostat ON
NO
Suction temperature
18 C[64 F]
YES
1. Heat source unit (compressor) intermittent operation
2. Indoor unit fan intermittent operations
(Synchronized with the compressor :
low speed, OFF operations)
[1] or [2]
- 147 -
Normal operation
Thermostat ON
Unit in the stopped state
*Note 2
*Note 1
[ VII Control ]