Electric Wiring - Haier AB242ACBEA Service Manual

Commercial air conditioning 24 28 universal outdoor unit air conditioning
Hide thumbs Also See for AB242ACBEA:
Table of Contents

Advertisement

5
In case of gas leakage, tighten
parts of pipe connection. If
No gas leakage?
leakage stops, then proceed
steps.
6
Detach the charge hose from the service port, open
2-way valve and 3-way. Turn the valve rod
anticlockwise until hitting lightly.
7
To prevent the gas leakage, turn the service port's
cap, the valve rod'd cap for 2-way valve and 3-way's
a lottle more than the point where the torque
increases suddenly.
8
After attaching the each caps, check the gas
leakage around the caps.
CAUTION:
If the refrigerant of the air conditioner leaks, it is necessary to
make all the refrigerant out, then charge the liquid refrigerant
into air conditioner according to the amount marked on the
name plate.
If needing to remove the refrigerant gas when installation or repair , please refer to the following procedures:
1. Cut off the power
2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again
and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure.
4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure
pressure-switch properly.

5. Electric wiring

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped
terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length
wires with less than 2% voltage drop.)
Item
Phase
Model
36,42 series, 28 series
(380-400V,3N~,50Hz)
14,18, 24, 28 series
(1PH,220-230V,50Hz)
If it does not stop gas leakage, discharge
whole refrigerants from the serice port.
After flaring work again and vacuumize,
6
fill up prescribed refrigerant from the gas
cylinder.
DANGER OF BODILY INJURY OR DEATH
Circuit breaker
Switch breaker
Overcurrent protector
(A)
rated capacity (A)
3
30
1
40
2-way valve
3-way valve
7
7
Valve rod cap
Service port cap
7
WARNING
Power source
wire size
(minimum)
20
2.5mm
26
4.0mm
2-way valve
3-way valve
6
For series 24,28
6
2-way valve
Liquid pipe 9.52mm
3-way valve
Gas pipe 19.05mm
6
For series 36,42
6
2-way valve
3-way valve
For series 24,28
Valve rod cap
7
Service port cap
7
Earth leakage breaker
Switch
Leak
breaker
current
2
30
30mA
2
40
30mA
For series 36,42
Valve rod cap