Haier AB242ACBEA Service Manual page 90

Commercial air conditioning 24 28 universal outdoor unit air conditioning
Hide thumbs Also See for AB242ACBEA:
Table of Contents

Advertisement

Failure code with wired controller YR-E12:
For
Failure
remote
code
on
type, flash
wired
times
controller
10
08
1
01
2
02
3
4A
4
49
5
48
6
53
8
07
9
06
11
0B
12
03
13
0D
15
05
For
central
Failure description
control,
failure code
21
Drainage system failure
01
Indoor ambient temp. sensor
failure
02
Indoor coil temp. sensor failure
11
Outdoor ambient temp. sensor
failure
12
Outdoor
failure
discharging temp. sensor)
10
Over-current protection
14
High pressure abnormal
06
Communication between wired
controller and indoor abnormal
05
Communication
indoor and outdoor abnormal
30
Outside alarm signal input
20
Gas
pipe
abnormal
31
Solenoid valve abnormal
17
EEPROM abnormal
Reason
Float switch broken down for more than
25m continuously
sensor broken down or short circuit for
more than 2m continuously
sensor broken down or short circuit for
more than 2m continuously
sensor broken down or short circuit for
more than 2m continuously
coil
temp.
sensor
Sensor broken down or short circuit for
(compressor
more than 2m continuously
CT check abnormal 3 times in 30m
High pressure switch acts 3 times in 30m
Communication abnormal for more than
4m continuously
between
Communication abnormal for more than
4m continuously
Outside signal broken down for more than
10s
temp.
sensor
Sensor broken down or short circuit for
more than 2m continuously
Solenoid valve act incorrectly 3 times
continuously
EEPROM data missing