11. Refrigerant pipe

[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause
water leakage.]
The outdoor unit has been charged with refrigerant.
When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown,
use spanner and torque spanner together.
When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use
hand to twist 3-4 rings, then fasten with spanner.
Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)
Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown.
Only use seal cushion to bind the joint part of air pipe and heat insulation parts.
Paste the refrigerant oil here
Torque spanner
Air inlet
Drain hose connection mouth
VP25 PVC pipe
Specification of pipe Tighten torque
(mm)
9.52
19.05
Middle size seal cushion (accessory)
(Use seal cushion to
bind the pipe joint)
Spanner
Pipe joint
Cone nut
80
Liquid pipe
Gas pipe
530
Cone dimension
A (mm)
3270~3990 N . cm
12.0~12.4
(333~407 kgf . cm)
9720~11860 N . cm
22.9~23.3
(990~1210 kgf . cm)
Clamp
Heat insulation (accessory)
(for liquid pipe)
Heat insulation (accessory)
(for gas pipe)
Gas pipe
Liquid pipe
510
Electric box
Upper
Air outlet
Down side
Cone
45
2
90 0.5
A
R0.4~0.8