2) The wire control organ displays the alarm signal with "E0"
"E0" means the floater switch of indoor unit is abnormal
3) The wire control organ displays the alarm signal with "E1"
"E1" means indoor ambient temperature sensor is abnormal
Notation: The resistance of indoor ambient sensor is 23K
begining
the alarm signal of wire
control organ is E0
if the floater swith is
orientated correctly
Y
if the function of the
floater is normal
N
replacing the switch
Figure 7-4
begining
wire control organ displays
the alarm signal with E1
if the indoor ambient sensor
is orientated correctly
Y
if the resistance of
sensor is right
N
replacing the sensor
Figure 7-5
-53-
N
amend the oritation of
the floater switch
amend the
N
position of the
sensor