TROUBLESHOOTING GUIDE
TROUBLESHOOTING GUIDE
STOVE FEEDS PELLETS, BUT WILL NOT IGNITE
Possible Causes:
1.
Air damper open too far for ignition.
2.
Blockage in igniter tube or inlet for igniter tube.
3.
The burnpot is not pushed completely to the rear of
the fi rebox.
4.
Bad igniter element.
The control board is not sending power to the igniter.
SMOKE SMELL COMING BACK INTO THE HOME
Possible Causes:
1.
There is a leak in the vent pipe system.
2.
The gasket on the combustion blower has gone
bad.
CONVECTION BLOWER SHUTS OFF AND COMES BACK ON
Possible Causes:
1.
The convection blower is overheating and
tripping the internal temperature shutoff.
2.
Circuit board malfunction.
Possible Remedies:
Push the air damper in closer to the side of the stove for
startup. In some situations, it may be necessary to have the
damper completely closed for ignition to take place. After
there is a fl ame, the damper can then be adjusted for the
desired feed setting.
Find the igniter housing on the backside of the fi rewall. The
air intake hole is a small hole located on the bottom side of
the housing. Make sure it is clear. Also, look from the front
of the stove to make sure there is not any debris around the
igniter element inside of the igniter housing.
Make sure that the air intake collar on the burnpot is touch-
ing the rear wall of the fi rebox.
Put power directly to the igniter element. Watch the tip of the
igniter from the front of the stove. After about 2 minutes, the
tip should glow. If it does not, the element is bad.
Check the voltage going to the igniter during startup. It
should be a full current. If the voltage is lower than full cur-
rent, check the wiring. If the wiring checks out good, the
board is bad.
Possible Remedies:
Inspect all vent pipe connections. Make sure they are
sealed with RTV silicone that has a temperature rating of
500
F or higher. Also, seal joints with UL-181-AP foil tape.
o
Also, make sure the square to round adapter piece on the
combustion blower has been properly sealed with the same
RTV.
Inspect both gaskets on the combustion blower to make
sure they are in good shape.
Possible Remedies:
Clean any dust off the windings and fan blades. If clearing
the blower does not help, the blower may be bad.
Test the current going to the convection blower. If there is
power being sent to the blower when it is shut off, the
control board is fi ne. If there is NOT power being sent to the
blower when it shuts off during operation, then you have a
bad control board.