Insert Installation; Check Gas Type; Install Gas To Insert Location; Installation Items Needed - Monessen Hearth ICFDV30LNTSC Installation And Operating Instructions Manual

Icfdv series direct vent gas fireplace insert
Table of Contents

Advertisement

ICFDV Fireplace Insert

CheCK GAS Type

Use proper gas type for the insert you are installing. If you have conflicting gas type, do not
install insert. See dealer where you purchased the insert for proper insert according to your
gas type.
INSTALL GAS pIpING TO INSeRT LOCATION
A qualified installer or service person must
connect appliance to gas supply. Follow all
local codes.

INSTALLATION ITeMS NeeDeD

Make sure you have the items listed below before installing appliance.
External regulator (supplied by installer)
Sealant (resistant to propane/LP gas)
Tee joint
approved flexible gas line with gas connector (if allowed by local codes — not provided)
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test
gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will
reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of wa-
ter. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external
regulator with the vent pointing down as shown in Figure 11. Pointing the vent down protects it from freezing
rain or sleet.
External
Regula-
tor
Vent
Pointing
Down
Figure 11 -
External Regulator with Vent Pointing Down
(Propane/LP Only)
14
Piping (check local codes)
Sediment trap (optional but recommended)
Pipe wrench
100 gal. (min.
Propane/LP
Supply Tank
FP1930

INSeRT INSTALLATION

For propane/Lp units, never connect insert
directly to the propane/Lp supply. This burn-
er system requires an external regulator
(not supplied). Install the external regulator
between the burner system and propane/Lp
supply.
Test gauge connection*
use only new black iron or steel pipe. Inter-
nally tinned copper or copper tubing can be
used per National Fuel Gas Code, Section
2.6.3, providing gas meets hydrogen sulfide
limits, and where permitted by local codes.
Gas piping system must be sized to provide
minimum inlet pressure (listed on data plate)
at the maximum flow rate (BTu/hr). undue
pressure loss will occur if the pipe is too
small.
20304164