Manual Setting By Remote Controller - Toshiba RAV-SM562KRT-E Service Manual

Hi wall type (indoor unit)
Hide thumbs Also See for RAV-SM562KRT-E:
Table of Contents

Advertisement

3. Address Setting
When determining indoor unit addresses with wiring completed without piping
construction
Wiring example of 2 refrigerant systems
(Solid line: wiring, broken line: refrigerant piping)
O/U
(Power cable only)
I/U
Refrigerant line
→ 1
address
→ 1
Indoor unit address
→ 1
Group address
For systems like this example, connect a wired remote controller
independently without connecting R/C wires, and then set these addresses.
Group address
Individual: 0000
Header unit: 0001
in case of group control
Follower unit: 0002
5
8
2
4
7
10
End
11
1
Operation procedure
1
2
3
4
8
9
10
11
O/U
(Power cable only)
I/U
I/U
I/U
I/U
1
1
2
2
2
3
1
2
2
2
2
2
3
6
9
5
6
7
End

(Manual setting by remote controller)

<Address setting procedure>
Connect a remote controller to the
indoor unit whose address you want to
set one to one.
Turn ON the power.
Press
1
simultaneously for 4 seconds or more.
Refrigerant
Set code
2
line address
Set a refrigerant line address with
3
buttons.
Press
4
normal operation.
Indoor unit
Set code
5
address
Set indoor unit addresses with
6
buttons.
Press
7
normal operation.
Group
Set code
8
address
Set indoor unit addresses with
9
buttons as follows:
Individual=
follower unit=
Press
10
normal operation.
Press
11
Indoor unit address setting is completed.
The operation mode returns to normal
OFF.
74
,
, and
on the R/C
with
buttons.
Indication on the LCD shows
with
buttons.
Indication on the LCD shows
with
buttons.
, header unit=
Indication on the LCD shows
.
,

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm802krt-eRav-sm5661krt-eRav-sm801krt-e