Toshiba RAV-SM562KRT-E Service Manual page 70

Hi wall type (indoor unit)
Hide thumbs Also See for RAV-SM562KRT-E:
Table of Contents

Advertisement

ON-SITE SETTING AND OTHERS
(2)
Manual setting/change of indoor unit refrigerant line addresses
[In the case of 30 refrigerant systems or more (when multiple air conditioners are included,
their number of refrigerant systems is also included)]
Regarding refrigerant systems up to No. 29, manual setting/change is the same as that on the
previous page.
• Refrigerant address "1" is assigned to all indoor units except for group control by the auto address
setting after system power on. Therefore, change refrigerant line address of each refrigerant
system using the wired remote controller.
• Also change indoor unit addresses so as to avoid duplication of indoor unit numbers.
Refrigerant line
address
Indoor unit
address
Group address
Refrigerant line
address
Indoor unit
address
Group address
* For changing/setting refrigerant line addresses by wired remote controller, refer to
SETTING.
* Change refrigerant line address of all indoor units connected directly to the central controller to
"30".
These indoor units are under twin or triple control, also change the refrigerant line address of
follower indoor units to "30".
* Change indoor unit addresses so that they are not duplicated.
Central
controller
Refrigerant
Refrigerant
system 30
system 31
O/U
O/U
I/U
I/U
R/C
R/C
1
1
1
1
0
0
1
2
1
1
0
0
Refrigerant
Refrigerant
system 32
system 33
O/U
O/U
I/U
I/U
I/U
R/C
R/C
1
1
1
1
2
1
1
2
1
3
3
4
1
2
1
1
2
1
69
Refrigerant
system 34
O/U
I/U
2
An example after auto address
1
setting
2
5
1
After changing refrigerant line
address manually
2
11
ADDRESS