Jøtul F 602 USA Installation And Operating Instructions Manual page 28

Table of Contents

Advertisement

Available languages

Available languages

Parallel installation in a corner with
Fig. 17
wall shield
Wall shield
• Must be 1" off the
wall and 1" off the
floor.
• With single wall
pipe, the shield
must be 49" high
measured off the
floor.
• With double wall
pipe, the shield
must be 37" high
measured off the
floor.
• Both shields MUST
extend and join in
the corner.
Corner installation with wall shield
Fig. 18
Wall shield
• Must be 1" off
the wall and 1"
off the floor.
• With single wall
pipe, the shield
must be 49".
• With the double
wall pipe, the
shield must be
37" high.
• Both shields
MUST extend
and join in the
corner.
Fig. 19
A
A: Lift to open
B: Left - closed, Right - open
(Measurements in cm - for Canada)
28
Combustible wall
The wall
shield must
extend a
minimum of
4" (102 mm)
past the side
of the stove
The wall shield must extend a mini-
mum of 7" (178mm) past the ash lip
of the stove
Combustible wall
The wall shield
must extend a
minimum of 7"
(178mm) past
the front corner
of the stove.
The wall shield must
extend a minimum of 7"
(178mm) past the front
corner of the stove.
B
Fig. 20
A
B
A: Unit to 8" Wide Mantel -
B: Unit to Top Trim -
C: Unit to Side Trim -
D: Unit to Side Wall -
C
D
30 in. (76 cm)
21 in. (53.5 cm)
18 in. (46 cm)
24 in. (61 cm)