Summary Of Ul Requirements - Gemini GEM-P816 Installation Instructions Manual

Control panel/communicator
Hide thumbs Also See for GEM-P816:
Table of Contents

Advertisement

Page 8
Smoke Detectors, 4-Wire:
1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Hochiki America SLG-12 with YBC-RL4-RA Base
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations and
thermostats may be used if acceptable to the Authority having Jurisdiction.
UL Compatible Smoke Detectors (Providing UL Recognition or Listing)
Manufacturer
Napco
Sentrol
449AT
449C
449CRT
449CST
449CSRT
449CSRH
449CSST
System
1112
Sensor
2112
Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10
**Maximum wire length for use with 2WTA-B
Solid FLPR or equivalent
18 AWG
16 AWG
14 AWG
Based on 10 ohm line resistance.

SUMMARY OF UL REQUIREMENTS

Residential
Recognized Limited-Energy Cable for initiating, indicat-
ing and supplementary circuits.
Initiating loops supervised if longer than 3 feet
FT2200 End-of-Line Relay for Fire (if using 4-wire
smoke detectors)
Minimum alarm timeout of 5 minutes
Maximum exit time: 60 seconds
Maximum entry time: 45 seconds
Do not program "Swinger Shutdown", "Force Arming",
"Selective Bypass" or "50 ms Loop Response"
"Abort Delay" may not exceed 45 seconds
Program "Disable Callback Download"
Automatic dialer may not dial a police station number
that has not been dedicated for such service
System must be tested at least weekly under AC/
GEM-P816 Installation Instructions
4-Wire
Smoke Detector
FW-4
449CLT
712U
449CSLT
722U
449CTE
732U
741U
711U
742U
721U
721UT
2112T
2100
2112TSRB
2100T
Maximum wire length for use with 2WTA-B
550 ft
1100 ft
1900 ft
2-Wire
Smoke Detector
Smoke Detector *
FW-2
731U
701U
702U
702RE
702RU
1100
2WTA-B**
When using the System Sensor RRS-MOD with the
2WTA-B, please see the Figure 5 wiring diagram from
the System Sensor RRS-MOD Installation Instructions
(D500-44-00/I56-2203-01) and the Figure 7 wiring dia-
gram from the System Sensor Maintenance Module In-
stallation Instructions (D500-46-00/I56-2174-002) to il-
lustrate the correct wiring.
Please note the proper placement of the 470 OHM resis-
tor in the Figure 5 wiring diagram of the RRS-MOD. In
addition, please use the Fire Power + terminal 25 in-
stead of the Aux. Power + terminal 5 in the Figure 7 wir-
ing diagram of the Maintenance Module.
battery and Battery-Only conditions
Replace the rechargeable battery at least every 5 years
If the battery is heavily discharged, replace it or have it
tested by a qualified technician
For silent panic, connect only to UL-listed holdup de-
vices
All zones must be programmed for "Priority"
Do not program any zones for "Keyswitch Arming"
System must be serviced at least once every year
Residential Fire and Combination Residential Fire &
Burglary must program "Residential Fire"
Keypad Expansion (EZM) Zones are not to be used as
fire zones
Keypad Auxiliary is not to be selected
The GEM-K Series Keypads must have the indicators
printed on the face label (Fire, Police and Auxiliary)
covered by a supplied label if not in use.
Base
IMPORTANT NOTICE