Summary Of Ul Requirements - Gemini GEM-P1664 Installation Instructions Manual

Control panel/communicator
Hide thumbs Also See for Gemini GEM-P1664:
Table of Contents

Advertisement

Page 8
Smoke Detectors, 4-Wire:
1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Hochiki America SLG-12 with YBC-RL4-RA Base
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations and
thermostats may be used if acceptable to the Authority having Jurisdiction.
UL Compatible Smoke Detectors (Providing UL Recognition or Listing)
Manufacturer
Napco
Sentrol
System
Sensor
Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10

SUMMARY OF UL REQUIREMENTS

Residential
Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.
Initiating loops supervised if longer than 3 feet
FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)
Minimum alarm timeout of 5 minutes
Maximum exit time: 60 seconds
Maximum entry time: 45 seconds
Do not program "Swinger Shutdown", "Force Arming", "Selective Bypass" or "50 ms Loop Response"
"Abort Delay" may not exceed 45 seconds
Program "Disable Callback Download"
Automatic dialer may not dial a police station number that has not been dedicated for such service
System must be tested at least weekly under AC/battery and Battery-Only conditions
Replace the rechargeable battery at least every 5 years
If the battery is heavily discharged, replace it or have it tested by a qualified technician
For silent panic, connect only to UL-listed holdup devices
All zones must be programmed for "Priority"
Do not program any zones for "Keyswitch Arming"
System must be serviced at least once every year
Residential Fire and Combination Residential Fire & Burglary must program "Residential Fire"
Keypad Expansion (EZM) Zones are not to be used as fire zones
Keypad Auxiliary is not to be selected
The GEM-K Series Keypads must have the indicators printed on the face label (Fire, Police and Auxiliary) covered by a
supplied label if not in use.
X
GEM-P1664 Installation Instructions
4-Wire
Smoke Detector
FW-4
449AT
449CLT
449C
449CSLT
449CRT
449CTE
449CST
741U
449CSRT
742U
449CSRH
449CSST
1112
2112T
2100
2112
2112TSRB
2100T
2-Wire
Smoke Detector
Smoke Detector *
FW-2
712U
731U
701U
722U
702U
732U
702RE
711U
702RU
721U
721UT
1100
L
WI1424A 1/06
Base
NAPCO Security Systems