Battery Charger
8.1.4
Battery temperature compensation
The battery charger has battery temperature compensation. The temperature is measured by
the external temperature sensor (see section 6.6 ).
28.5 / 56.9
27.2 / 54.4
26.2 / 52.4
Figure 8.4 Temperature compensation for Vfloat
The temperature compensation for V
For PLN-24CH12: -40 mV /
For PRS-48CH12: -80 mV /
8.2
Commissioning the system
NOTICE!
To avoid start-up problems of the battery charger, the main and auxiliary output current
should be < 12 A.
Use the following procedure to commission the system:
1.
2.
3.
4.
Bosch Security Systems B.V.
V float
-20
-10
0
10
o
C @ 25
o
C @ 25
Switch-on the mains circuit breaker (battery fuse breaker is off).
Check the output voltage on the main and auxiliary outputs:
–
PLN-24CH12: ≈ 27.3 Vdc
–
PRS-48CH12: ≈ 54.6 Vdc
Switch-on the battery fuse breaker L (Refer to table 6.1 ). After approx. 2.5 seconds the
battery relay is activated.
The battery charger is operating correctly when the 3 LEDs on the front panel are green.
If not, refer to the troubleshoot section 9 .
Installation and Operation manual
20
30
40
50
60
is:
float
o
C.
o
C.
Operation | en
70
Temp
180110011Aa | V1.1 | 2011.05
29