en | Configuration
7

Configuration

7.1

Battery charging

CAUTION!
If a mains failure occurs either on the battery charger, the connected system or on both (the
system turns on 'back-up operating' mode, mains not present condition) an alarm must be
generated on the Voice Alarm System.
In normal operating mode: the battery charger (re)charges the batteries and maintains them
when they are fully charged. The maximum current that can be provided to the main outputs
and auxiliary outputs is Imax a.
In back-up operating mode: the total operating current is provided by the batteries and
battery charger (when mains present) and may not exceed 'Imax b.
Imax a
Imax b
Authorized batteries
If Imax b is greater than 100 A, use batteries with a capacity of 86 Ah to 225 Ah and set
daughter board jumper on '75' (see Figure 5.1).
If Imax b is less than 100 A, use batteries with a capacity of 65 Ah to 225 Ah, and set daughter
board jumper on '50' (see Figure 5.1).
The following batteries are approved:
180110011Aa | V1.1 | 2011.05
Maximum available current which may be drawn continuously while charging
the battery:
- Imax a = 12 A - Icharge.
- Icharge = C/20 (C = battery capacity)
Maximum allowed current which may be drawn from the batteries when the
mains supply is not available on one or more of the system units:
- Imax b = 150 A if the jumper is set on '75'
- Imax b = 100 A if the jumper is set on '50' (see Figure 5.1).
Yuasa NPL series
Powersonic GB series
ABT TM series
Enersys VE series
Effekta BTL series
Long GB series.