8. TROUBLESHOOTING

A. BOILER ERROR
1. When an error condition occurs the controller will
display an error code on the display module.
2. These error codes and several suggested corrective
actions are included in Table 8.1.
3. In the case of E00, E13, and E14 this error, if
uncorrected, will go into a fault condition as
described is Paragraph B.
B. BOILER FAULT
1. When a fault condition occurs the controller will
illuminate the red "fault" indication light and display
a fault code in the format "F##" on the display
module.
2. Note the fault code and refer to Table 8.2 for an
explanation of the fault code along with several
suggestions for corrective actions.
3. Press the reset key to clear the fault and resume
operation. Be sure to observe the operation of the
unit to prevent a recurrence of the fault.
WARNING
When servicing or replacing any components of this
boiler be certain that:
The gas is off.
All electrical power is disconnected
Table 8.1: P125 Control Board Error Codes
Code
Description
E00
High Limit Exceeded
Combustion Fan Speed Low.
E13
The boiler combustion air fan speed
less than 70% of expected.
Combustion Fan Speed High.
E14
The boiler combustion air fan speed
is more than 130% of expected.
PRO
Water Pressure Switch Open
FLu
Blocked Vent Pressure Switch Open
When servicing or replacing components that are in
direct contact with the boiler water, be certain that:
There is no pressure in the boiler. (Pull the
release on the relief valve. Do not depend on
the pressure gauge reading).
The boiler water is not hot
The electrical power is off
Do not use this appliance if any part has been under
water. Improper or dangerous operation may result.
Contact a qualified service technician immediately to
inspect the boiler and to repair or replace any part of
the boiler which has been under water.
This appliance has wire function labels on all internal
wiring. Observe the position of each wire before
removing it. Wiring errors may cause improper and
dangerous operation. Verify proper operation after
servicing.
If overheating occurs or the gas supply fails to shut
off, do not turn off electrical power to the circulating
pump. This may aggravate the problem and increase
the likelihood of boiler damage. Instead, shut off the
gas supply to the boiler at the gas service valve.
Duration
1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by
accessing the status menu and assuring that there is less
50 Sec.
than a 50°F rise from the return thermistor to the supply
thermistor.
3. Replace switch if faulty.
1. Check the combustion air fan wiring.
60 Sec.
2. Replace the combustion air fan.
3. Replace the control board.
1. Check the combustion air fan wiring.
60 Sec.
2. Replace the combustion air fan.
3. Replace the control board.
1. Assure that the system pressure is above 10 psig.
2. Check for leaks in the system piping.
Until Corrected
3. Check the switch operation by applying a jumper. (If the
switch is not functioning properly replace it.)
1. Assure that the vent is not blocked.
Until Corrected
2. Check the switch operation by applying a jumper. (If the
switch is not functioning properly replace it.)
TROUBLESHOOTING
DANGER
WARNING
CAUTION
CAUTION
Corrective Action
33