BDV Series Gas Fireplace
StANDING pILOt IGNItION
SyMptOM
4. Frequent pilot
outage problem.
5. The pilot and main
burner extinguish
while in operation
6. Glass Soots
7. Flame burn blue
and lifts off burner
(ghosting)
5
pOSSIBLE cAuSE
A. Pilot flame may be too high
or too low, causing pilot
safety to drop out
A. Inner vent pipe leaking
exhaust gases back into
system
B. Horizontal vent improperly
pitched
C. Improper vent cap installa-
tion
A. Flame impingement on logs
A. Insufficient oxygen being
supplied
ActION
A. Clean and adjust the pilot flame for maximum flame
impingement on thermocouple.
A. Check for flue product leak. Replace defective pipe sec-
tion.
B. Check horizontal-venting piping is running upward 1/4" per
foot. Do not run the pipe level or downward.
C. Check for proper installation and freedom from debris or
blockage.
A. Install log set per the instructions
Inspect the injector and air intake area. Make sure this area
does not have any blockage from debris and clean.
Check gas supply.
A. Ensure that the vent cap is installed properly and free of
debris. Ensure that the vent system joints are tight and
have no leaks. Ensure that no debris has been blocking
the inner air intake at the bottom back of the combustion
chamber. Ensure that the glass is properly secure and
latch.

tROuBLEShOOtING

54D0700