Table of Contents

Advertisement

BDV Direct Vent
Gas Fireplace
Models:
BDV300, BDV400,
BDV500, BDV600
WARNING
IF the INFoRMAtIoN IN these INstRuctIoNs Is Not
FolloWeD exActly, A FIRe oR explosIoN MAy
Result cAusING pRopeRty DAMAGe, peRsoNAl
INjuRy oR loss oF lIFe.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
WhAt to Do IF you sMell GAs
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed
by a qualified installer, service agency or the
gas supplier.
WARNING: Improper installation, adjustment, alteration,
services or maintenance can cause injury or property
damage. Refer to this manual. For assistance or additional
information consult a qualified installer, service agency
or the gas supplier.
this appliance may be installed in an aftermarket*,
permanently located, manufactured home (usA only) or
mobile home, where not prohibited by local codes.
this appliance is only for use with the type of gas
indicated on the rating plate. this appliance is not
convertible for use with other gases, unless a certified
kit is used.
* Aftermarket: completion of sale, not for purpose of resale, from the
manufacturer.
540701
DVB cover
Due to hIGh teMpeRAtuRes, the ApplIANce
shoulD Be locAteD out oF tRAFFIc AND
AWAy FRoM FuRNItuRe AND DRApeRIes.
chIlDReN AND ADults shoulD Be AleRteD
to t h e h A Z A R D s o F h I G h s u R FA c e
teMpeRAtuRe AND shoulD stAy AWAy to
AVoID BuRNs oR clothING IGNItIoN.
youNG chIlDReN shoulD Be supeRVIseD
WheN they ARe IN the sAMe RooM As the
ApplIANce.
clothING oR otheR FlAMMABle MAteRIAl
shoulD Not Be plAceD oN oR NeAR the
ApplIANce.
Keep the RooM AReA cleAR AND FRee FRoM
coMBustIBle MAteRIAls, GAsolINe, AND
otheR FlAMMABle VApoRs AND lIquIDs.
INstAlleR: leave this manual with the appliance.
coNsuMeR: Retain this manual for future refer-
ence.
54D0700 7/09 Rev. 14

Advertisement

Table of Contents
loading

Summary of Contents for Monessen Hearth BDV300

  • Page 1 BDV Direct Vent Gas Fireplace Models: BDV300, BDV400, BDV500, BDV600 WARNING IF the INFoRMAtIoN IN these INstRuctIoNs Is Not FolloWeD exActly, A FIRe oR explosIoN MAy Result cAusING pRopeRty DAMAGe, peRsoNAl INjuRy oR loss oF lIFe. – Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
  • Page 2: Table Of Contents

    coNteNts BDV Series Direct Vent Gas Fireplace thank you and congratulations on your purchase of a Monessen Fireplace. pleAse ReAD the INstAllAtIoN AND opeRAtIoN INstRuctIoNs BeFoRe usING the ApplIANce! IMpoRtANt: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty. Important safety Information ........3 operating Instructions - Milli-Volt ......31 Lighting Pilot for the First Time ......31...
  • Page 3: Important Safety Information

    BDV Series Direct Vent Gas Fireplace IMpoRtANt sAFety INFoRMAtIoN oWNeR INstAlleR Please retain these instructions for future reference. Please leave these instructions with the appliance. • Read this owner’s manual carefully and completely before trying to assemble, operate, or service this fireplace. •...
  • Page 4: Code Approval

    BDV Series Direct Vent Gas Fireplace IMpoRtANt sAFety INFoRMAtIoN 1. Do not use this fireplace to cook food or burn paper IMpoRtANt: or other objects. pleAse ReAD the FolloWING 13. Never place anything on top of fireplace. cAReFully 14. Do not use any solid fuels (wood, coal, paper, card- board, etc.) in this fireplace.
  • Page 5: Product Features

    BDV600NE Nat. 6,000 0,000 Optional Remote Figure 1 - Receiver BDV600PE 6,000 0,000 1.55 mm BDV300/400/500/600 Fireplace BDV600NSC Nat. 6,000 0,000 (Millivolt control shown) BDV600PSC 6,000 0,000 1.55 mm hIGh eleVAtIoNs Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370 m) above sea level.
  • Page 6: Fireplace & Framing Dimensions

    O - Min. Rough Opening Width Min. Rough Opening Height 5/8" 1/2” 1/2” 5/8" Figure 2 - 3 ” Fireplace & Framing Dimensions 8 ” BDV300 BDV400 BDV500 BDV600 33Z\zn” (840 mm) 37Z\zn” (941 mm) 41Z\zn” (1043 mm) 47Z\zn” (1195 mm) 540701 9M\,” (759 mm) 3”...
  • Page 7: Pre-Installation Information

    pRe-INstAllAtIoN INFoRMAtIoN BDV Series Direct Vent Gas Fireplace BeFoRe you stARt FIReBox FRAMING Read this homeowner manual thoroughly and follow all Firebox framing can be built before or after the appliance instructions carefully. Inspect all contents for shipping is set in place. Refer to Figure 2 for firebox and framing damage and immediately inform your dealer if any damage dimensions.
  • Page 8: Fireplace Location

    BDV Series Direct Vent Gas Fireplace pRe-INstAllAtIoN INFoRMAtIoN FIReplAce locAtIoN Plan for the installation of your appliance. This includes determining where the unit is to be installed, the vent configuration to be used, framing and finishing details, and whether any optional accessories (i.e.
  • Page 9: Clearances

    cleARANces BDV Series Direct Vent Gas Fireplace cleARANces to coMBustIBles Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire hazard. the appliance cannot be installed on a carpet, tile or other combustible material other than wood flooring. If installed on carpet or vinyl flooring, the appliance shall be installed on a metal, wood or noncombustible material panel extending full width and depth of the appliance.
  • Page 10: Secure Fireplace To Floor Or Framing

    BDV Series Direct Vent Gas Fireplace secuRe FIReplAce to FlooR or FRAMING The fireplace must be secured to the floor and/or to framing studs as shown in Figure 6. Use two () wood screws or masonry/ concrete screws to secure fireplace to the floor. Use four (4) screws to attach fireplace to framing.
  • Page 11: Optional Top Vent Application

    VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace optIoNAl top VeNt ApplIcAtIoN The appliance is shipped as a rear vent unit. If the installa- After conversion to top vent configuration, tion layout requires the unit to be a top vent configuration the 4”...
  • Page 12: Venting Installation

    VeNtING INstAllAtIoN INFoRMAtIoN BDV Series Direct Vent Gas Fireplace Read all instructions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life. operation of improperly installed and maintained venting system could result in serious injury, property damage or loss of life.
  • Page 13: Installation Planning

    VeNt INstAllAtIoN BDV Series Direct Vent Gas Fireplace INstAllAtIoN plANNING Never run the vent pipe down. this may cause There are two basic types of direct-vent installation: excessive temperatures which could cause a • Horizontal Termination fire. • Vertical Termination It is important to select the proper length of vent pipe for the type of termination you choose.
  • Page 14: Termination Locations

    VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace GeNeRAl VeNtING INFoRMAtIoN - teRMINAtIoN locAtIoN INSIDE  CORNER DETAIL  G  V  H  A  D  E  L  C  B  B  V  Fixed B  V  Closed V  Fixed Operable Closed F  V  B  M  V  B ...
  • Page 15: How To Use The Vent Graph

    VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace teRMINAtIoN cleARANces FoR BuIlDINGs WIth coMBustIBle AND NoNcoMBustIBle exteRIoRs G=6" (152mm) F=6" (152mm) Inside Corner  Outside Corner  C = Maximum depth of 48" (1219mm)     for alcove location D = Minimum width for back wall of     alcove location     Combustible - 38" (965mm)     Noncombustible - 24" (610mm) E = Clearance from corner in alcove  Combustible &      location Noncombustible  ...
  • Page 16: Rear (Through-The-Wall) Applications

    VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace ReAR (thRouGh the WAll) ApplIcA- . Locate and cut the vent opening in the wall. For com- tIoNs bustible walls first frame in opening. combustible Interior Walls: Cut a 11Z\x"H x 9Z\x" W When installed as a rear vent unit this appliance may be hole through the interior wall.
  • Page 17: Horizontal Termination Configurations

    BDV Series Direct Vent Gas Fireplace VeNtING INstAllAtIoN Interior Wall Surface Vent Cap (Horizontal Termination) Firestop Vent Cap FP1957 FP1955 Horizontal Screw Vent Pipe Apply Mastic to Wood Screw All Four Sides Figure 19 - Install Firestop on Horizontal Vent Pipe Figure 17 - hoRIZoNtAl teRMINAtIoN coNFIGuRA- Install Horizontal Termination...
  • Page 18 VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace 36" When installing the appliance as a rear 36" (914 mm) vent unit, the 90° or 45° transition elbow (914 mm) Max. Max. attached directly to the rear of the unit is Not INcluDeD in the following criteria and calculations and, unless specifically mentioned, should be ignored when...
  • Page 19: Below Grade Installation

    VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace If installing a snorkel, a minimum 4" vertical rise is neces- sary. The maximum horizontal run with the 4” vertical pipe is 36". This measurement is taken from the collar of the B: 7’...
  • Page 20: Vertical Through-The-Roof Applications

    VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace Support Straps Every 3’ Snorkel 40’ Maximum Height 8’ Minimum Height Foundation 10’ Maximum Recess Wall Screws Support Straps Sheet Metal Watertight Seal Every 3’ Screws Around Pipe FP1966 Figure 27 - 10’...
  • Page 21: Installation For Vertical Termination

    VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace • Drop the disk into a 4" inner collar before installing the first section of flue or install at the last section before installing the termination. • An additional disk may be installed on runs of 35' or more.
  • Page 22: Cathedral Ceiling Installation

    BDV Series Direct Vent Gas Fireplace VeNtING INstAllAtIoN material. Make sure to meet the minimum allowable " clearances to combustibles. Do not fill any of the " required clearance spaces with insulation. cAtheDRAl ceIlING INstAllAtIoN 1. Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box.
  • Page 23: Flex Venting Installation

    Flex VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace 1. Flexible UL1777 listed venting may be used in any 3. Start the flexible vent as follows: venting application where rigid direct vent compo- A. Installing the inner flex adapter and pipe. Figure nents can be used.
  • Page 24: Flex Vent Installation

    Flex VeNtING INstAllAtIoN BDV Series Direct Vent Gas Fireplace 5. Flexible vent spacers are to be installed at intervals . Slide termination cap adapter ring over the termi- prescribed by the flexible vent manufacturer; and in nation cap's outside pipe and secure with three such a way as to maintain concentric inner and outer screws.
  • Page 25: Fireplace Installation

    BDV Series Direct Vent Gas Fireplace FIReplAce INstAllAtIoN checK GAs type Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or conversion kit.
  • Page 26 BDV Series Direct Vent Gas Fireplace FIReplAce INstAllAtIoN A manual shutoff valve must be installed only persons licensed to work with gas upstream of the appliance. union tee and piping may make the necessary gas plugged 1/8” Npt pressure tapping point connections to this appliance.
  • Page 27: Check Gas Pressure - Millivolt

    MIllIVolt & electRoNIc checK GAs pRessuRe and electRIcAl INstAllAtIoN BDV Series Direct Vent Gas Fireplace 1. Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance.
  • Page 28: Remote Wall Switch Installation

    electRIcAl INstAllAtIoN BDV Series Direct Vent Gas Fireplace ReMote WAll MouNteD sWItch A remote wall switch and up to fifteen (15) feet of 18 Ga. wire may be used with this appliance. Attach the wall switch in a junction box at the desired location on the wall. Figure 42. Do not extend beyond the wall switch wire length provided.
  • Page 29: Electronic Pilot Ignition Wiring

    electRIcAl INstAllAtIoN BDV Series Direct Vent Gas Fireplace electRoNIc pIlot IGNItIoN WIRING Do not connect 110-120V Ac to the Remote Wall switch. the appliance will malfunction. To Junction Box  Pilot Assembly  GREEN Ignition Module Spark WHITE BLACK Sense Electronic Valve  RED #2  BLACK WHITE Primary - 120V  GRAY #1 RED #2 ...
  • Page 30: Optional Fan/Blower Systems - Milli-Volt

    BDV Series Direct Vent Gas Fireplace optIoNAl FAN / BloWeR systeM optIoNAl FAN/BloWeR systeMs (Blot) The junction box for the fan/blower systems has been factory installed. This system requires that 110-10 VAC to be wired to the factory installed junction box before the fireplace is permanently installed.
  • Page 31: Operating Instructions (Millivolt)

    opeRAtING INstRuctIoNs (MIllIVolt) BDV Series Direct Vent Gas Fireplace FoR youR sAFety ReAD BeFoRe lIGhtING If you do not follow these instruction exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance is equipped with a pilot which must be lit with built-in piezo ignitor while following these instructions exactly.
  • Page 32: Lighting Pilot

    opeRAtING INstRuctIoNs (MIllIVolt) BDV Series Direct Vent Gas Fireplace lIGhtING pIlot FoR the FIRst tIMe AppRoVeD leAK testING MethoD If using a soap and water You may check for gas leaks with the following methods solution to test for leaks, only: Do Not spray solution onto •...
  • Page 33: Lighting Burner

    opeRAtING INstRuctIoNs (MIllIVolt) BDV Series Direct Vent Gas Fireplace lIGhtING BuRNeR MAIN BuRNeR sWItch The “ON/OFF/RS” switch for the main burner can be found behind door of the fireplace. This switch allows you to turn on and to turn off the main burner without using the gas valve knob. Make sure the button is in the “ON”...
  • Page 34: Operating Instructions - Electronic

    opeRAtING INstRuctIoNs (electRoNIc) BDV Series Direct Vent Gas Fireplace FoR youR sAFety ReAD BeFoRe lIGhtING This appliance is equipped with an ignition device If you do not follow these (Piezo) which automatically lights the pilot. Do NOT instructions exactly, a fire or try to light the burner by hand.
  • Page 35: Check Gas Pressure - Signature Command System

    BDV Series Direct Vent Gas Fireplace sIGNAtuRe coMMAND - checK GAs pRessuRe and electRIcAl INstAllAtIoN 1. Check gas type. The gas supply must be the same as Pressure Inlet stated on the appliance’s rating decal. If the gas supply is different from the fireplace, stop! Do not install the appliance.
  • Page 36: Command Center Wall Installation

    BDV Series Direct Vent Gas Fireplace sIGNAtuRe coMMAND - electRIcAl INstAllAtIoN OPTIONAL AC BOX TO JUNCTION BOX IN FIREPLACE PILOT OPTIONAL LIGHT WHITE BLACK OPTIONAL WHITE BLOWER BLACK BLACK OPTIONAL WHITE GREEN CONNECTOR PIN TO CONTROL BOX INPUT 300 WATT MAX EACH RF RECEIVER ON/OFF BUTTON CONTROL BOX...
  • Page 37: Optional Fan/Blower System

    optIoNAl FAN BloWeR systeM BDV Series Direct Vent Gas Fireplace optIoNAl FAN/BloWeR systeM (Blotsc) Installation Instructions Wiring 10V AC 1. Before installing the blower, wire the receptacle into an 60Hz electrical circuit. This should be done before framing the fireplace. Wire with minimum 60° C wire in accordance with Factory Supplied prevailing codes.
  • Page 38 optIoNAl FAN BloWeR systeM BDV Series Direct Vent Gas Fireplace 7. Secure the AC box to the control box using Screw screw provided. Figure 56 Ac Box 8. Plug in wiring harness to the back of AC box. 9. Connect the blower according to the wiring diagram.
  • Page 39: Operating Instructions - Signature Command System

    BDV Series Direct Vent Gas Fireplace opeRAtING INstRuctIoNs - sIGNAtuRe coMMAND FoR youR sAFety ReAD BeFoRe lIGhtING If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of lie. A.
  • Page 40: Operating Instructions

    BDV Series Direct Vent Gas Fireplace opeRAtING INstRuctIoNs - sIGNAtuRe coMMAND opeRAtING INstRuctIoNs 1. stop! Read the safety information above. . This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. 3.
  • Page 41: Signature Command System Operation

    sIGNAtuRe coMMAND systeM opeRAtIoN INstRuctIoNs BDV Series Direct Vent Gas Fireplace FeAtuRes To Thermopile RF Receiver ON/OFF To Sensor command center To Sparker • Easy Access Function Operation and System Configu- ration NG/LP • Operation Confirmation/Fault Diagnostic Indications Conversion (LED/Buzzer) •...
  • Page 42 sIGNAtuRe coMMAND systeM opeRAtIoN INstRuctIoNs BDV Series Direct Vent Gas Fireplace systeM coNFIGuRAtIoN/setup System configuration/setup is done on the Command Center. Intermittent/standing pilot setup (Default intermittent) 1. Holding the ON button on the Command Center while turning on the master switch will toggle between standing pilot and intermittent pilot.
  • Page 43 sIGNAtuRe coMMAND systeM opeRAtIoN INstRuctIoNs BDV Series Direct Vent Gas Fireplace FuNctIoNs/opeRAtIoN turning on the fireplace 1. Turn on the master switch and wait for a beep. . Press the ON button on the Command Center. Pilot will light and burner will come on High setting. pilot safety lockout Function 1.
  • Page 44: Glass Removal

    GlAss ReMoVAl BDV Series Direct Vent Gas Fireplace GlAss FRAMe ReMoVAl 1. Release two clamps on bottom of fireplace. Figure 59 . Tilt glass frame out and lift glass frame up until it clears three tabs on top of fireplace. 3.
  • Page 45: Final Installation

    Do not sprinkle the lava rock or ember chunks on top of the burner. this may cause potential sooting, glass breakage and a fire Center Vertical Grate Bar hazard. LG619 Figure 61 - Right Vertical Log Placement Grate Bar (BDV300 & BDV400 Shown) 54D0700 LG619...
  • Page 46: Cleaning And Maintenance

    BDV Series Direct Vent Gas Fireplace cleANING and MAINteNANce turn off gas before servicing fireplace. It is recommended that a qualified service technician Thermocouple perform these check-ups at the beginning of each heating season. Thermopile BuRNeR, pIlot AND coNtRol coMpARtMeNt Keep the control compartment, logs, and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year.
  • Page 47: Vent System

    cleANING and MAINteNANce BDV Series Direct Vent Gas Fireplace VeNt systeM The fireplace and venting system should be inspected before initial use and at least annually by a qualified field service person. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow.
  • Page 48: Standing Pilot Ignition

    tRouBleshootING BDV Series Direct Vent Gas Fireplace stANDING pIlot IGNItIoN syMptoM possIBle cAuse ActIoN 1. Spark ignitor will A. Wire disconnected. A. Open door and check to make sure wire is connected not light pilot after to ignitor. repeated triggering of B.
  • Page 49 tRouBleshootING BDV Series Direct Vent Gas Fireplace stANDING pIlot IGNItIoN syMptoM possIBle cAuse ActIoN 4. Frequent pilot A. Pilot flame may be too high A. Clean and adjust the pilot flame for maximum flame outage problem. or too low, causing pilot impingement on thermocouple.
  • Page 50: Signature Command System

    tRouBleshootING BDV Series Direct Vent Gas Fireplace sIGNAtuRe coMMAND systeM ACTION OPERATION FAULT DIAGNOSIS Using Battery polarity wrong? Re-install batteries battery? Make sure Command Install batteries and/or Battery voltage low? Change batteries Center and plug in the AC board No beep in about the control 8 seconds board are...
  • Page 51: Replacement Parts

    ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace FIReBox coMpoNeNts 540701 DVB parts 54D0700...
  • Page 52 ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace FIReBox coMpoNeNts Item Description qty. BDV300 BDV400 BDV500 BDV600 standard Features Junction Box 6D18K 6D18K 6D18K 6D18K Black Louver 54D046 6D0695 6D0697 6D0699 Glass Frame Assembly 54D094 54D0195 54D0340 54D0443 Factory Installed options...
  • Page 53: Standing Pilot Millivolt Control

    ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace stANDING pIlot - MIllIVolt coNtRol 11,12,13,14 540701 DVB millivolt parts 54D0700...
  • Page 54 ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace stANDING pIlot - MIllIVolt coNtRol Item Description qty. BDV300NV BDV300pV BDV400DNV BDV400pV BDV500NV BDV500pV BDV600NV BDV600pV Gas Valve Assy. 37D0117 37D0118 37D0117 37D0118 37D0117 37D0118 37D0117 37D0118 Pilot Assembly 37D0018 37D0019 37D0018 37D0019 37D0018 37D0019...
  • Page 55: Electronic Ignition

    ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace electRoNIc IGNtIoN 540701 DVB elect parts 54D0700...
  • Page 56 ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace electRoNIc IGNtIoN Item Description qty. BDV300Ne BDV300pe BDV400Ne BDV400pe BDV500Ne BDV500pe BDV600Ne BDV600pe 1. Gas Valve Assy. 37D0016 37D0017 37D0016 37D0017 37D0016 37D0017 37D0016 37D0017 . Pilot Assembly 37D000 37D001 37D000 37D001 37D000 37D001 37D000...
  • Page 57: Signature Command System

    ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace sIGNAtuRe coMMAND systeM 13, 14, 15 540701 SC parts 54D0700...
  • Page 58 (not shown) FAI83/4 19. Mesh Glass Cover (not shown) BDV300SD BDV400SD BDV500SD BDV600SD Fuel conversion Kits - signature command system Natural Gas to lp BDV300 Kit #BCK300CKPS BDV400 Kit #BCK400CKPS BDV500 Kit #BCK500CKPS BDV600 Kit #BCK600CKPS lp to Natural Gas BDV300...
  • Page 59: Vent Components

    ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace VeNt coMpoNeNts 540701 DVB vent components 54D0700...
  • Page 60 ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace VeNt coMpoNeNts current simpson simpson Duravent Duravent qty./ or Mhsc or Mhsc selkirk Item Description part no. part no. part no. Side Wall Flexible Pipe Termination Kit BHSFTKA BHSFTK Includes termination cap with built-in vinyl siding standoff, heat deflector, firestop, 0"...
  • Page 61: Logs

    ReplAceMeNt pARts BDV Series Direct Vent Gas Fireplace loGs Ref. Description qty. BDV300 BDV400 BDV500 BDV600 1. Rear Log #1 54D011 54D0181 54D0339 54D0339 540700 . Top Right Log # 54D0147 54D0116 54D0361 54D0361 BDV logs 3. Top Left Log #3...
  • Page 62: Mass Residents Only

    Massachusetts Residents only — please read and follow these special requirements BDV Series Direct Vent Gas Fireplace . Approved carbon Monoxide Detectors. Each carbon Note ReGARDING VeNteD pRoDucts monoxide detector as required in accordance with the above This product must be installed by a licensed plumber or gas fitter provisions shall comply with NFPA 70 and be ANSI/UL 034 when installed within the Commonwealth of Massachusetts.
  • Page 63: Warranty

    BDV Series Direct Vent Gas Fireplace lIMIteD lIFetIMe WARRANty polIcy lIFetIMe WARRANty The following components are warranted for life to the original owner, subject to proof of purchase: Firebox, Combustion Chamber, Heat Exchanger, Grate and Stainless Steel Burners. FIVe yeAR WARRANty The following components are warranted five (5) years to the original owner, subject of proof of purchase: Ceramic Fiber Logs.
  • Page 64: Energuide

    efficiency Ratings Model enerGuide Ratings Fireplace efficiency (%) BDV300NV 57.9 BDV300PV 53.8 BDV300NE 61.8 BDV300PE 55.7 BDV400NV 58.4 BDV400PV 58.5 BDV400NE 61.1 BDV400PE 60.7 BDV500NV 58.7 BDV500PV 58.8 BDV500NE 61.3 BDV500PE 60.8 BDV600NV 58.4 BDV600PV 58.5 BDV600NE 60.9 BDV600PE 60.5 Mhsc 149 Cleveland Drive •...