Infinite SCOM-100 User Manual page 37

Infinite alarming & remote control unit user guide scom-100
Hide thumbs Also See for SCOM-100:
Table of Contents

Advertisement

SCOM-100, User guide
ALH:
u:
d:
For example let us explain all the different parameter
settings to use a 4-20mA, 0-10 bar pressure sensor wired
on analog input 2 on the main unit (See section 2.4.2).
The pressure sensor characteristic is shown in the
diagram below:
The 4-20mA input signal is converted by the internal A/D
converter in the digital raw range of 819 to 4095.
37
Alarm high limit in physical units
(number in the range of SCL to SCH
with one optional decimal digit.
Example: ALH = 121.5)
Physical unit (0-15 characters)
Delay time in seconds (0-65535)

Advertisement

Table of Contents
loading

Related Products for Infinite SCOM-100

Table of Contents