Quadra-Fire Expression 36 Owner's Manual page 17

Qv36a-fb
Hide thumbs Also See for Expression 36:
Table of Contents

Advertisement

2. Top Vent - Vertical Termination - (continued)
Three Elbows
Note: A section of vertical pipe (12 inches minimum)
MUST be installed prior to attaching a 90° elbow.
V
2
Figure 5.8
H
2
INSTALLED
HORIZONTALLY
Quadra-Fire • Expression 36 (QV36A-FB) • 2062-900 Rev. Q • 2/10
V
T
H
T
H
V
Min.
H
T
1 ft. 6 in.
2 ft. 6 in.
3 ft. 6 in.
4 ft.
4 ft. 6 in.
5 ft. 6 in.
6 ft. 6 in.
7 ft. 6 in.
H
= 21 ft. Max
T
V
= 40 ft. Max
T
V
+ H
= 30 ft. Max*
T
T
* If the horizontal component is less than
5 feet then the total vent run can be
extended to 40 feet.
1
V
1
Max.
T
3 ft.
6 ft.
9 ft.
10 ft.
12 ft.
15 ft.
18 ft.
21 ft.
17