10-3. Outdoor Unit (RAS-18UAX, RAS-18UA-AR)

No.
Part name
1
Common
procedure
2
Running
capacitor for
compressor
3
Running
capacitor for
fan motor
4
Relay
5
Spark killer
Procedures
1) Stop the operation of the air conditioner
and turn off its main power supply or
remove the power supply wires.
2) Remove the electrical parts cover.
(4 screws)
3) Remove the cord clamps. (4 screws)
4) Remove the connecting cables after
removing 7 screws on the terminal block.
5) Remove the front cabinet. (8 screws)
• Pull the front lower portion toward you
and pull out it upward to remove it.
6) Remove the back cabinet and side cabinet.
(12 screws)
1) Remove the capacitor band. (1 screw)
2) Disconnect the lead wires from the
capacitor terminal.
1) Remove the capacitor band. (1 screw)
2) Disconnect the lead wires from the
capacitor terminal.
1) Unlatch the relay and pull it upward.
2) Disconnect the lead wires from the relay
terminal.
1) Remove the spark killer. (1 screw)
2) Disconnect the lead wire from the terminal
block.
Front cabinet
P.C. board
– 56 –
FILE NO. SVM-01010
Remarks
Electrical parts
cover
Side cabinet
Running capacitor
for compressor
Running capacitor
for Fan motor
Relay
Transformer