Outdoor Unit (Ras-30N2A-Ar) - Toshiba RAS-30NKP2B-1 Service Manual

Table of Contents

Advertisement

4-3. Outdoor Unit (RAS-30N2A-AR)

No.
Parts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
5
Magnetic contactor
Type
Output (Rated) 2700 W, 2 poles, 1 phase, 220 - 240 V, 50 Hz
Winding resistance (Ω)
NH56VNHT
(at 25°C)
Output (Rated) 42 W, 6 poles, 1 phase, 220 - 240 V, 50 Hz
Winding resistance (Ω)
MMF-230-65I
(at 20°C)
AC 450 V, 3.5µF
451355L
RSS44B606U0220S AC 440 V, 60µF
220 - 240 V, 50 Hz
A35
– 10 –
FILE NO. SVM-06017
Specifications
C-R
0.66
1.58
Red-Black
White-Black
71.2
139.0
C-S

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ras-30n2a2bRas-30n2a-arRas-30nkp-ar-1