Powervar ACDEF700-11 User Instruction Manual

Powervar ACDEF700-11 User Instruction Manual

Sinergy iii rackmount / tower
Table of Contents

Advertisement

POWERVAR Sinergy III Rackmount / Tower User Instruction Manual
·
ACDEF700-11
·
ACDEF1000-11 1000 VA UPS
·
ACDEF1500-11 1500 VA UPS
·
ACDEF2000-11 2000 VA UPS
·
ACDEF3000-11 3000 VA UPS
· ACDEF2000-22 2000 VA UPS
· ACDEF3000-22 3000 VA UPS
This manual contains important instructions for the Sinergy III UPS and External Battery
Cabinets. Follow these instructions during the unpacking, installation, and maintenance of the
UPS and the External Battery Cabinet. If you have a problem with the UPS or the battery
cabinet, please refer to this manual before calling technical support.
POWERVAR
1450 South Lakeside Drive
Waukegan, IL 60085-8301
T (847) 596-7000
(800) 369-7179
F (847) 596-7100
www.powervar.com
A01-00040 Rev. E
Sinergy III 120 Volt UPS
700 VA UPS
· E024-12 External Battery Cabinet
· E036-12 External Battery Cabinet
· E048-12 External Battery Cabinet
· E072-12 External Battery Cabinet
Sinergy III 200-240 Volt UPS
· E048-12 External Battery Cabinet
· E072-12 External Battery Cabinet

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACDEF700-11 and is the answer not in the manual?

Questions and answers

Summary of Contents for Powervar ACDEF700-11

  • Page 1 POWERVAR Sinergy III Rackmount / Tower User Instruction Manual Sinergy III 120 Volt UPS · ACDEF700-11 700 VA UPS · ACDEF1000-11 1000 VA UPS · E024-12 External Battery Cabinet · ACDEF1500-11 1500 VA UPS · E036-12 External Battery Cabinet ·...
  • Page 2 A01-00040 Rev. E...
  • Page 3: Table Of Contents

    2.5 Environmental Conditions …………………………………………………………………………... 2.6 Floor Loading ……………………………………………………………………………………….. 2.7 Ventilation ………………………………………………………………………………………….. 2.8 Rear Panel View …………………………………………………………………………………….. 2.8.1 Models : ACDEF700-11, ACDEF1000-11, ACDEF1500-11 …………………………………….. 2.8.2 Model : ACDEF2000-11 ………………………………………………………………………….. 2.8.3 Model : ACDEF3000-11 ………………………………………………………………………….. 2.8.4 Model : ACDEF2000-22 ………………………………………………………………………….. 2.8.5 Model : ACDEF3000-22……………………………………………………………………………...
  • Page 4 UPS Operation …………………………………………………………………………………………. 5.1 UPS input connection ………………………………………………………………………………... 5.1.1 LCD Display in Bypass Mode……………………………………………………………………… 5.1.2 LCD Display in Standby Mode…………………………………………………………………….. 5.2 Turn on the UPS (Put the UPS in OnLine Mode) …………………………………………………… 5.2.1 LCD Display in OnLine Mode …………………………………………………………………….. 5.3 Connect Devices to the UPS ………………………………………………………………………… 5.4 The UPS in Battery Mode ……………………………………………………………………………...
  • Page 5: Introduction

    (800) 369-7179 F (847) 596-7100 Please check with technical support before attempting to repair or return any POWERVAR product. If a POWER- VAR UPS needs repair or replacement, technical support will issue a return material authorization (RMA) number along with instructions on how to return the UPS.
  • Page 6: Safety

    These battery extensions may only be connected to the compatible basic UPS unit. 1.5.2 General Warnings CAUTION: POWERVAR considers the safety of personnel to be of paramount importance. For this reason it is essential that procedures relating to safety in this manual be carefully reviewed before commencing work , and properly adhered to later.
  • Page 7 The units are heavy. Lifting the units into the rack requires a minimum of two people. · When installing units in racks, do not allow racks to become “top heavy”. Install heaviest equip- · ment (typically the external battery cabinet) near bottom of rack, and install this equipment before installing equipment higher in the rack.
  • Page 8: Battery Safety

    1.5.4 Battery Safety IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS CAUTION: The batteries installed in the UPS and within the extended battery cabinets contain electro- lyte. Under normal conditions the containers are dry. A damaged battery may leak electrolyte that can be dangerous when in contact with the skin and cause irritation to the eyes.
  • Page 9: Overview

    Please keep the original package in a safe place for future use. 2.1 UPS Devices and Batteries The following table provides an overview of the various versions of the device: Sinergy III UPS Model Battery Cabinet Model ACDEF700-11 E024-12 ACDEF1000-11 E024-12 ACDEF1500-11 E036-12...
  • Page 10: Recharging The Ups During Storage

    2.4 Recharging the UPS During Storage Before storing, charge the UPS for five hours. During storage, recharge the battery in accordance with the follow- ing table: Storage Temperature Recharge Frequency Charging Duration -13°F to 104°F (-25°C to +40°C) Every 3 Months 1-2 Hours 104°F to 113°F (40°C to +45°C) Every 2 Months 1-2 Hours...
  • Page 11: Rear Panel View

    2.8 Rear Panel View 2.8.1 Models : ACDEF700-11, ACDEF1000-11 and ACDEF1500-11 2.8.2 Model : ACDEF2000-11 2.8.3 Model : ACDEF3000-11...
  • Page 12: Model : Acdef2000-22

    2.8.4 Model : ACDEF2000-22 2.8.5 Model : ACDEF3000-22 1. Programmable Output Receptacles 2. Direct Output Receptacles 3. AC Input 4. Input Circuit Breaker 5. Emergency Power Off Function Connector (EPO) 6. USB Communication Port 7. RS232 Communication Port 8. SNMP Intelligent Slot 9.
  • Page 13: External Battery Cabinet

    2.8.4 External Battery Cabinet 9. External Battery Connector 10. Output Circuit Breaker 11. Serial Number...
  • Page 14: Lcd Display

    2.9 LCD Display 2.9.1 Rack Display Load Info Battery Info Warning & Fault Input/Output Info/Setting and Battery Operation Info UPS Status Backup Time Info 2.9.2 Tower Display Battery Info Input/Output and Battery Info Warning & Fault Info/ Setting Operation UPS Status Load Info Backup Time Info...
  • Page 15: Lcd : Display And Functional Description

    2.10 LCD : Display and Functional Description Display Function Backup time information Indicates the backup time. Indicates the backup time. H: hours, M: minutes Warning & Fault information Indicates that a warning and/or fault has occurred. Indicates the warning and fault codes. The codes are listed in sections 9.4 and 9.5.
  • Page 16: Installation

    3. Installation The UPS and external battery cabinet are designed to be rack-mounted in four post frames or to be floor standing in a tower configuration. 3.1 Tower Installation   ATTENTION: Use all supplied mounting hardware on each UPS and extended battery cabinet. A.
  • Page 17: Rack Installation

    3.2 Rack Installation The UPS and the external battery cabinets are designed to be rack-mounted in four post frames. The UPS and ex- ternal battery cabinet use identical mounting hardware and procedures. NOTE: The rack-mount UPS draws air from the front. If the rack has a door on the front, make sure that there is some clearance between the UPS vents and the rack door.
  • Page 18 Step 2. Use four M6 screws to mount the right and left rail sliders to the two back posts of the four-post rack. Refer to the figure directly below : Step 3. Insert one M6 nut into the right and left front posts of the four-post rack for a 2U installation. Refer to figure directly below : Step 4.
  • Page 19: Electrical Preparations

    CAUTION: Column one in the table below lists each of the UPS models and column two displays the corresponding model of the extended battery cabinet which must be used with the UPS. DO NOT USE any other extended battery cabinet for the corresponding UPS. UPS Model Battery Cabinet Model ACDEF700-11 E024-12 ACDEF1000-11 E024-12 ACDEF1500-11...
  • Page 20 NOTE: Each battery cabinet contains two battery connectors. The first battery cabinet is connected to the UPS using the cable supplied with the cabinet. Each additional extension battery cabinet is connected by attaching its cable to the previous cabinet. Refer to the figure below. If additional battery cabinets (up to 4) are to be used, they should be connected prior to connecting the UPS to the input power.
  • Page 21: Setting Up Ups Parameters

    4. Setting Up UPS Parameters 4.1 Factory Default Settings The UPS is shipped with the following default factory settings. Refer to the table below and also to the table “LCD Display Abbreviation Index” in Section 9.3. FACTORY DEFAULT SETTING PARAMETER 100 - 120 Volt Models 200 - 240 Volt Models Output Voltage...
  • Page 22: Output Voltage Setting (Item 01)

    1. Press and hold the “SELECT” button for at least five seconds to enter the UPS setting mode. 2. Press the “UP” or the “DOWN” button to scroll thru all of the parameters itemized as (01, 02, 03, 06, 07, 08, 09, 10 and 11).
  • Page 23: Output Frequency Setting (Item 03)

    4.2.3 Output Frequency Setting (Item 03) Interface Setting You may set the initial frequency on battery mode: 50: output frequency is 50Hz 60: output frequency is 60Hz If converter mode is enabled , the following output frequency can be chosen: 50: output frequency is 50Hz 60: output frequency is 60Hz 4.2.4 Bypass Mode Enable /Disable when the UPS is off (Item 06)
  • Page 24: Programmable Outlets Setting (Item 08)

    4.2.6 Programmable Outlets Setting (Item 08) Setting Interface 0-999: Backup time in minutes that programmable output receptacles will operate in battery mode. 4.2.7 LCD Display Direction Setting (Item 09) Interface Setting RAC: the LCD display is horizontal. TOE: the LCD display is vertical. 4.2.8 Acceptable Input Voltage Range Setting (Item 10) Interface Setting...
  • Page 25: Ups Operation

    5. UPS Operation 5.1 UPS Input Connection Plug the input of the UPS into a two-pole, three-wire, grounded receptacle. Avoid using extension cords.   ATTENTION: This UPS is supplied with standard power cords and receptacles suitable for use in your area of operation. It may be installed and operated by non-technical personnel. If the mains voltage is within the acceptable range, and the bypass is enabled the UPS will enter bypass mode.
  • Page 26: Turn On The Ups (Put The Ups In Online Mode)

    5.2 Turn on the UPS (Put the UPS in On-Line Mode) When the input voltage is within the acceptable range press and hold the “ON/Mute” button for at least two sec- onds. A few seconds later the UPS will turn on and enter on-line mode. “ONLINE” will be displayed in the UPS status window on the LCD display.
  • Page 27: The Ups In Battery Mode

    5.4 The UPS in Battery Mode 1) When the input voltage is not within the acceptable range or there is a mains failure the UPS will enter battery mode. The batteries will continue to provide an uninterrupted supply of energy to the load. 2) When the UPS is in battery mode the LCD display panel will display the battery level by 0-25%, 26-50%, 51-75% and 76-100% and the battery voltage.
  • Page 28: Interfaces

    6. INTERFACES The UPS’s are equipped with a serial interface COM 3, USB and a interface slot COM. These interfaces can be used for : 1. Direct communication between UPS and a workstation/server. 2. Integration of the UPS as client into a network with centralized monitoring via a Manage UPS SNMP adaptor in the slot COM.
  • Page 29: Emergency Power Off (Epo)

    7. Emergency Power Off (EPO) Disable and Enable the EPO Function Keep Pin 1 and Pin 2 closed (shorted) for UPS normal operation. To activate the EPO function, remove the wire between Pin 1 and Pin 2. Pin 1 and Pin 2 shown in closed status.
  • Page 30: Replacing Batteries

    .4 Replacing Batteries The UPS does not require maintenance by the user, however, battery maintenance is recommended in accordance with IEEE Recommended Practice for Maintenance, Testing and Replacement of Valve- Regulated Lead-Acid (VRLA) Batteries for Stationary Applications (IEEE Std 1188-1996). When the batteries expire, trained battery service personnel must replace them.
  • Page 31 This UPS is equipped with internal batteries. The user can replace the batteries without shutting down the UPS or connected loads (hot-swappable battery design). Replacement is a safe procedure - isolated from electrical hazards.   ATTENTION: Consider all warnings, cautions, and notes before replacing batteries. ·...
  • Page 32 5. Slide in replacement battery pack. Refer to the figure directly below : 6. Reconnect the battery connectors. Use the tie wrap supplied with the replacement battery kit to secure the two halves of the battery connector together. Re-install the battery retention plate using the screws removed in step 3. Refer to the figures directly below : 7.
  • Page 33: Troubleshooting

    9. Troubleshooting If the UPS system does not function properly, please resolve the problem by referring to the table below and on the following page. 9.1 Troubleshooting Table Symptom Possible cause Remedy No warning or fault indication and no alarm even The AC input power cord Confirm that the AC input though the mains is normal.
  • Page 34 Symptom Possible cause Remedy Fault code is shown as 43 and the icon The UPS shut down automati- Remove excess loads from UPS cally because of an overload output and restart it. appears on the LCD on the output of the UPS. display.
  • Page 35: Audible Alarm

    9.2 Audible Alarm Alarms Beeps Once Every Four Seconds Battery Mode Alarm Beeps Once Every Second Low Battery Alarm Beeps Twice Every Second Overload Alarm Beeps Continuously Fault 9.3 LCD Display Abbreviation Index Abbreviation Display Content Meaning Enable Disable Escape Rack Display Tower Display Low Battery...
  • Page 36: Warning Indicators

    9.4 Warning Indicators Warning Icon (flashing) Code Alarm Low Battery Beeps Once Every Second Overload Beeps Twice Every Second Battery is Not Connected Beeps Once Every Second Overcharge Beeps Once Every Second Site Wiring Fault Beeps Once Every Second EPO Enable Beeps Once Every Second Over Temperature Beeps Once Every Second...
  • Page 37: Ups Fault

    9.5 UPS Fault When there is a fault with the UPS the fault icon flashes on the LCD display. A fault code will also be displayed directly below the flashing fault icon. When a fault occurs no output power is supplied from the UPS. 9.5.1 LCD Display in Fault Mode Rack Display Tower Display...
  • Page 38: Appendix A: Specifications

    10. APPENDIX A: SPECIFICATIONS 10.1 SINERGY III UPS (100 - 120 Volt UPS’s) Specifications Sinergy III Series UPS 700 VA Low Voltage Model ACDEF700-11 Part Number 17071-01R Type Sinergy III Power Rating 700 VA / 630 W Topology On-Line Double Conversion...
  • Page 39 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 40 SPECIFICATIONS CONT. SINERGY III UPS (100 - 120 Volt UPS’s) specifications cont. Sinergy III Series UPS 1000 VA Low Voltage Model ACDEF1000-11 Part Number 17101-01R Type Sinergy III Power Rating 1000 VA / 900 W Topology On-Line Double Conversion Heat Dissipation (BTU/Hour) 520 at 100% Load Input Voltage (Nominal) 100-120 VAC...
  • Page 41 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 42 SPECIFICATIONS CONT. SINERGY III UPS (100 - 120 Volt UPS’s) specifications cont. Sinergy III Series UPS 1500 VA Low Voltage Model ACDEF1500-11 Part Number 17151-01R / 17151-02R Type Sinergy III Power Rating 1500 VA / 1350 W Topology On-Line Double Conversion Heat Dissipation (BTU/Hour) 877 at 100% Load Input Voltage (Nominal)
  • Page 43 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and workman- ship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 44 SPECIFICATIONS CONT. SINERGY III UPS (100 - 120 Volt UPS’s) specifications cont. Sinergy III Series UPS 2000 VA Low Voltage Model ACDEF2000-11 Part Number 17201-01R / 17201-02R / 17201-03R Type Sinergy III Power Rating 2000 VA / 1800 W Topology On-Line Double Conversion Heat Dissipation (BTU/Hour) 1171 at 100% Load...
  • Page 45 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 46 SPECIFICATIONS CONT. SINERGY III UPS (100 - 120 Volt UPS’s) specifications cont. Sinergy III Series UPS 3000 VA Low Voltage Model ACDEF3000-11 Part Number 17301-01R / 17301-02R Type Sinergy III Power Rating 3000 VA / 2700 W Topology On-Line Double Conversion Heat Dissipation (BTU/Hour) 1756 at 100% Load Input Voltage (Nominal)
  • Page 47 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 48: Sinergy Iii Ups (200 - 240 Volt Ups) Specifications

    SPECIFICATIONS CONT. 10.2 SINERGY III UPS (200 - 240 Volt UPS) Specifications Sinergy III Series UPS 2000 VA High Voltage Model ACDEF2000-22 Part Number 17202-01R Type Sinergy III Power Rating 2000 VA / 1800 W Topology On-Line Double Conversion Heat Dissipation (BTU/Hour) 1000 at 100% Load Input Voltage (Nominal) 200-240 VAC...
  • Page 49 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 50 SPECIFICATIONS CONT. SINERGY III UPS (200 - 240 Volt UPS’s) specifications cont. Sinergy III Series UPS 3000 VA High Voltage Model ACDEF3000-22 Part Number 17302-01R Type Sinergy III Power Rating 3000 VA / 2700 W Topology On-Line Double Conversion Heat Dissipation (BTU/Hour) 1500 at 100% Load Input Voltage (Nominal) 200-240 VAC...
  • Page 51 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and workman- ship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 52: Extension Battery Cabinets For Use With Sinergy Iii Ups's

    Sinergy III Series Battery Cabinet 700 / 1000 VA Low Voltage Model E024-12 Part Number 17888-02R Type Sinergy III Compatible UPS ACDEF700-11 / ACDEF1000-11 Voltage (Nominal) 24.0 VDC 12V Flame Retardant Battery Type Sealed Lead-Acid Battery Quantity 2 x 2 Strings 24 Hours...
  • Page 53 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 54 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 55 SPECIFICATIONS CONT. Extension battery cabinets for use with Sinergy III specifications cont. Sinergy III Series Battery Cabinet 2000 VA High / Low Voltage Model E048-12 Part Number 17888-04R Type Sinergy III Compatible UPS ACDEF2000-11 / ACDEF2000-22 Voltage (Nominal) 48.0 VDC 12V Flame Retardant Battery Type Sealed Lead-Acid...
  • Page 56 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 57 SPECIFICATIONS CONT. Extension battery cabinets for use with Sinergy III specifications cont. Sinergy III Series Battery Cabinet 3000 VA High / Low Voltage Model E072-12 Part Number 17888-05R Type Sinergy III Compatible UPS ACDEF3000-11 / ACDEF3000-22 Voltage (Nominal) 72.0 VDC 12V Flame Retardant Battery Type Sealed Lead-Acid...
  • Page 58 Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work- manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWERVAR on the batteries.
  • Page 59: Appendix B: Optional Isolated Relay Contacts Card

    11. APPENDIX B: Optional Isolated Relay Contacts Card Model ISO-BASIC POWERVAR Part Number 17999-01R Installation and Operation 11.1 Description The isolated relay contacts card is an auxiliary interface card which provides isolated dry contact signals that indicate the status of the UPS to a locally connected system. The card also has a isolated input that the locally connected system can use to shut down the UPS.
  • Page 60: Isolated Relay Contact Card Operation

    11.3 Isolated Relay Contact Card Operation The isolated contacts interface card (see Figure B4) is an auxiliary interface card which provides isolated dry contact signals which indicate: Failure of AC source into the UPS. • A low battery-charge state when the UPS is running from battery. •...
  • Page 61: Isolated Relay Contact Card Functional Diagrams

    11.4 Isolated Relay Contact Card Functional Diagrams Figure B8 : Simplified Schematic of Interface Connections Function AC FAIL NC AC FAIL NO LOW BATTERY NC LOW BATTERY NO BYPASS ALARM COMMON SHUTDOWN (+) SHUTDOWN (-)
  • Page 62: Isolated Relay Contact Card Specifications

    • • Meridian 1 XII System Messages (PO842845) For POWERVAR Sinergy III Series UPS only: Alarm condition 1 should be interpreted as AC fail, inverter on. • Alarm condition 2 should be interpreted as an indication of low battery condition. This condition is a normal •...
  • Page 63: Appendix C: Warranty

    (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of shipment from POWER- VAR on the batteries. This warranty is limited to repairing, replacing, or refurbishing, at POWERVAR’s option, any defective component, circuit board or module within the Product.

Table of Contents