Connect Two Or More Domes - Vidia PTZ User Manual

Dome camera
Table of Contents

Advertisement

8.3
As the RS485 supports multi-drop topology, two or more devices can be connected
to one controller as a system. For such application, the rules must be followed:
Connect all speed domes to host in daisy chain pattern as possible as you can
Star type configuration should be avoided to keep system away from
instability.
Each speed dome must have its unique ID so communication data can be
delivered to the correct target device.
Impedance-match setup is also required to keep RS485 communication
quality.
Make wire distribution
Connect the other end of the cable to a phone box with extension outlet of two.
Installer must pay attention to the pins of the extension box to ensure the
connection is correct.
To connect more cameras, copy the same procedure on
above. You may continue extending the quantity of camera
to its maximum number of 128 per network, if the control
device has the capability of addressing that many ID..
The extension wire and box are available in general electronic and phone shops.
Vidia Srl – Via Vasanello 23, 00189 Roma – Tel +39 0630316333 Fax +39 0630350231 www.vidia.it
Connect two or more domes to console
RS-485
Extension
Box
Extension
Box
More Extension Box
Extension box
Speed
Dome
Speed Dome