Checking Voltage - Amana PHB**C Service Instructions Manual

Package heat pumps/gas/coolers
Table of Contents

Advertisement

SERVICING
S-1 CHECKING VOLTAGE
HIGH VOLTAGE
D
ALL
ISCONNECT
POWER BEFORE SERVICING OR
M
INSTALLING THIS UNIT.
ULTIPLE POWER SOURCES MAY
F
BE PRESENT.
AILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
1. Remove doors, control panel cover, etc. from unit being
tested.
With power ON:
L
INE VOLTAGE NOW PRESENT.
2. Using a voltmeter, measure the voltage across terminals
L1 and L2 of the contactor for single phase units, and L3,
for 3 phase units.
3. No reading - indicates open wiring, open fuse(s), or no
power to unit from fused disconnect service. Repair as
needed.
4. With ample voltage at line voltage connectors, energize
the unit.
5. Measure the voltage with the unit starting and operating,
and determine the unit Locked Rotor Voltage. NOTE: If
checking heaters, be sure all heating elements are ener-
gized.
Locked Rotor Voltage is the actual voltage available at
the compressor during starting, locked rotor, or a stalled
condition. Measured voltage should be above minimum
listed in chart below.
To measure Locked Rotor Voltage attach a voltmeter to
the run "R" and common "C" terminals of the compres-
sor, or to the T
and T
1
the unit and allow the compressor to run for several sec-
onds, then shut down the unit. Immediately attempt to
restart the unit while measuring the Locked Rotor Volt-
age.
6. Should read within the voltage tabulation as shown. If
the voltage falls below the minimum voltage, check the
line wire size. Long runs of undersized wire can cause
low voltage. If wire size is adequate, notify the local
power company in regards to either low or high voltage.
UNIT SUPPLY VOLTAGE
VOLTAGE
460
208/230
WARNING
WARNING
terminals of the contactor. Start
2
MIN.
MAX.
437
506
198
253
NOTE: When operating electric heaters on voltages other
than 240 volts refer to the System Operation section on elec-
tric heaters to calculate temperature rise and air flow. Low
voltage may cause insufficient heating.
Three phase units require a balanced 3 phase power supply
to operate. If the percentage of voltage imbalance exceeds
3% the unit must not be operated until the voltage condition
is corrected.
Max. Voltage Deviation
% Voltage =
From Average Voltage
Imbalance
Average Voltage
To find the percentage of imbalance, measure the incoming
power supply.
L1 - L2 = 240V
L1 - L3 = 232V
L2 - L3 = 238V
Total
710V
To find Max. deviation:
Max deviation was 4.7V
% Voltage Imbalance = 4.7
236.7
If the percentage of imbalance had exceeded 3%, it must be
determined if the imbalance is in the incoming power supply
or the equipment. To do this rotate the legs of the incoming
power and retest voltage as shown below.
L1
L2
L3
L1
L2
L3
By the voltage readings we see that the imbalance rotated or
traveled with the switching of the incoming legs. Therefore
the problem lies within the incoming power supply.
X 100
Avg. V = 710 = 236.7
3
240 - 236.7 = +3.3
232 - 236.7 = -4.7
238 - 236.7 = +1.3
= 1.99%
L1 - L2 = 240V
L1 - L3 = 227V
L2 - L3 = 238V
Rotate all 3 incoming
legs as shown.
L1 - L2 = 227V
L1 - L3 = 238V
L2 - L3 = 240V
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents