Ice-O-Matic ICE0250 Series Service And Installation Manual page 20

The ice series cubers
Hide thumbs Also See for ICE0250 Series:
Table of Contents

Advertisement

ICE Series
Remote Condenser Installation
For proper operation of the Ice-O-matic ice machine, the following installation guidelines must be
followed. Failure to do so may result in loss of production capacity, premature part failure, and
may void all warranties.
Installation Guidelines
Ambient operating temperatures: -20°F (-28.9°C) to 120°F (48.9°C)
Maximum refrigerant line length:
Maximum vertical rise:
Minimum condenser height:
installed more than 6 feet (1.3 meters) below the refrigerant line quick connects at the rear of the
ice machine. No part of the refrigerant lines, between the ice machine and the remote
condenser, should fall below this point. Condensers must have a vertical airflow.
Air Flow
60 ft. (18.29 Meters)
16 ft. (4.88 Meters)
ICE Series ice machine remote condensers must not be
Page A18
General Information

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ice1406*a1Ice1406*r1Ice1406*w1Ice1406*w2Ice1406*r2Ice1406*a3 ... Show all

Table of Contents