Final System Set Up - Trane Voyager YS 150–300 Installation, Operation And Maintenance Manual

Packaged rooftop – gas/ electric 121/2 – 25 tons, 60/50hz air conditioners
Table of Contents

Advertisement

Start Up
Figure 32. RTAM module
1
2
IGV - OFF OFF
VFD - ON OFF
OFF ON
VAV w/o IGV
ON ON
3
4
No Reset
OFF OFF
Return Air OFF ON
Zone Temp ON OFF
Outdoor Air ON ON
Supply Air Heating
Setpoint
5
DWU Disable OFF
DWU Enable ON
R 75
Supply air
cooling
setpoint
DIP switch
12345
ON
SW1
1
2
3
4
5
SW1
Supply Air (Static) Pressure S.P.
Supply Air Cooling Setpoint
Supply Air Reset Amount
Supply Air (Static) Pressure Deadband
Morning Warmup Setpoint
Supply Air Reset Setpoint
Supply Air Heating Setpoint

Final System Set Up

After completing all of the pre-start and start-up
procedures outlined in the previous sections (i.e.,
operating the unit in each of its modes through all
available stages of cooling and heating), perform these
final checks before leaving the unit:
Program the Night Setback (NSB) panel (if applicable)
for proper unoccupied operation. Refer to the
programming instructions for the specific panel.
Verify that the Remote panel "System" selection
switch, "Fan" selection switch, and "Zone
Temperature" settings for automatic operation are
correct.
Inspect the unit for misplaced tools, hardware, and
debris.
Verify that all exterior panels including the control
panel doors and condenser grilles are secured in place.
Close the main disconnect switch or circuit protector
switch that provides the supply power to the unit's
terminal block or the unit mounted disconnect switch.
40
Static
Static
pressure
pressure
setpoint
deadband For remote deadband cut
R64
R67
Reset
setpoint
R66
Morning
warmup
Reset
setpoint
amount
R68
R69
R63
1 2 3 4 5 6 7 8 9 10 11 12
13 14
this jumper
Remote setpoint
terminal strip
RT-SVX26K-EN