Service parameter(s) 20-21
20 Optimization based on room / outdoor temperature
Circuit
(I) / (II)
The optimized start and stop time can be based on either room or
outdoor temperature.
ON: Optimization based on room temperature, if
OFF: Optimization based on outdoor
21 Total stop
Circuit
I / (II)
Decide whether you want a total stop during the setback
temperature period.
ON: The desired flow temperature is lowered
OFF: No total stop
Setting range
ON / OFF
measured.
temperature. Use this setting if the room
temperature is not measured.
Setting range
ON / OFF
to 10 °C. The min. setting of the flow
temperature (line 2, section 22) is overruled.
Desired flow
temp. (°C)
10 °C
Desired flow
temp. (°C)
10 °C
32e
Factory setting
(OFF) / (OFF)
Factory setting
OFF / (OFF)