Installation Guide

Installer system test

During installer setup, press t
repeatedly until "Test" appears.
Shaded areas below apply only to P340-1320.
System test
1
Cooling system
2
Fan system
3
Heating system
4
Emergency
heating system
CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed
during testing. To prevent equipment damage, avoid cycling the compressor quickly.
69-2268—03
Test
number
Press DONE to terminate testing.
System status
0
Compressor and fan turn off
1
Compressor and fan turn on
2
Second stage compressor turns on
0
Fan turns off
1
Fan turns on
0
Heat and fan turn off
1
Heat turns on (fan on if Function 0170 is set for heat pump,
or if Function 0180 is set to "1") ** See page 6
2
Second stage heat turns on
3
Third stage heat turns on
0
Heat and fan turn off
1
Heat and fan turn on
2
Second stage heat turns on (Auxiliary heat)]
10
Press st to
select test
Press st to
change status
M29127
System
status
570-219