Security Chimneys International EPA BIS ULTRA Installation And Operating Instructions Manual page 20

Hide thumbs Also See for EPA BIS ULTRA:
Table of Contents

Advertisement

Facing
1. Combustible material must be installed flush with the fireplace. It may not project in
front of and on the fireplace (i.e. the steel façade of the fireplace) (figure 12).
2. Non-combustible materials such as brick, stone or ceramic tile may project in front of
and onto the fireplace facing (figure 13).
Mantel
The mantel must be installed at least 45" (1143 mm) above the base of the fireplace (figure
12).
Figure 12
Figure 13
16