Electrical Data - Carrier 38TXA Product Data

With r-410a 60 hz sizes 024 thru 048
Hide thumbs Also See for 38TXA:
Table of Contents

Advertisement

Electrical data

UNIT SIZE-
SERIES
V/PH
024-0
030-0
036-0
208/230/1
042-0
048-0
* Permissible limits of the voltage range at which unit will operate satis-
factorily.
† Time-delay fuse or HACR breaker.
‡ Length shown is as measured 1 way along wire path between unit and
service panel for voltage drop not to exceed 2%.
** If wire is applied at ambient greater than 30°C (86°F), consult Table
310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-
sheathed cable (NM), trade name ROMEX, shall be that of 60°C
(140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If
other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insula-
tion, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used, consult applicable tables of the NEC
(ANSI/NFPA 70).
OPER VOLTS*
Max
Min
LRA
61.0
72.5
253
187
83.0
109.0
109.0
COMPR
FAN
RLA
FLA
13.5
0.73
14.7
0.73
15.4
1.1
18.6
1.1
20.5
1.4
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, Refrigeration
LRA
— Locked Rotor Arms
MCA — Minimum Circuit Amps
RLA
— Rated Load Amps
NOTE: Control circuit is 24-v on all units and requires external power
source. Copper wire must be used from service disconnect to unit. All
motors/compressors contain internal overload protection.
MIN WIRE
MAX
SIZE
LENGTH (Ft)
60°C/75°C**
60°C/75°C‡
MCA
17.6
14/14
44/42
19.2
14/14
41/39
20.2
12/12
62/59
24.2
10/10
80/76
27.0
10/10
73/70
MAX FUSE†
OR HACR
TYPE CKT
BKR AMPS
25
30
30
40
40
7