VLI31 Fireplace Insert
cLeARANceS
MINIMuM FIRePLAce SIZe/cLeARANceS tO cOMBuStIBLeS
The dimensions shown on Pages 8 and 9, Figures 3 and 4, are mini-
mum clearances to maintain when installing this heater. Follow these
instructions carefully to ensure safe installation. Failure to follow
instructions exactly can create a fire hazard.
INSeRt cLeARANceS
No combustibles (ie: drapes, doors) may be within, or swing within 36" of the front of the insert.
Figure 3 -
Mantel Clearances
MANteL cLeARANceS
NOte: the combustible area above the facing must not protrude more than 3/4" from the
facing. If it does, it is considered a mantel and must meet the mantel requirements listed
in this manual.
heARth RequIReMeNtS
The insert must be installed on a noncombustible hearth extending a minimum of 1" from the
fireplace opening (local codes may require a larger hearth). The hearth must also extend to both
sides of the face (Refer to the table on Page 7).
8
Side Wall
10" (254 mm)
Minimum
12" (305 mm)
Minimum
42" (1067 mm)
Minimum
FP1947
insert clearances
9/08
12" (305 mm)
Maximum Depth
12"
(305 mm)
9"
(228 mm)
cLeARANceS
3/4" (19 mm)
Maximum Depth
Combustible Facing
NOte: Side clearance to com-
bustibles is 10" (54 mm) from
opening whether it is side wall
or mantel legs.
FP678
83D4009