Guide Specifications General; Products - Carrier CA16NA 018-061 Product Data

Single-stage air conditioner with puron refrigerant
Table of Contents

Advertisement

GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor- -mounted, air- -cooled, split- -system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a
hermetic
compressor,
an
air- -cooled
condenser fan, and a control box. Unit will discharge supply air
upward as shown on contract drawings. Unit will be used in a
refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition
of AHRI Standard 210.
— Unit will be certified for capacity and efficiency, and
listed in the latest AHRI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
standards and will carry the UL label of approval. Unit
will have c- -UL- -us approval.
— Unit cabinet will be capable of withstanding Federal
Test Method Standard No. 141 (Method 6061) 500- -hr
salt spray test.
— Air- -cooled condenser coils will be leak tested at 150
psig and pressure tested at 450 psig.
— Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is
stored
and
handled
recommendations.
Warranty (for inclusion by specifying engineer)
— U.S. and Canada only.

PRODUCTS

Equipment
Factory assembled, single piece, air- -cooled air conditioner unit.
Contained within the unit enclosure is all factory wiring, piping,
controls, compressor, refrigerant charge Puronr (R- -410A), and
special features required prior to field start- -up.
Unit Cabinet
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
coil, propeller- -type
per
unit
manufacturer's
AIR- -COOLED, SPLIT- -SYSTEM AIR CONDITIONER
Fans
— Condenser fan will be direct- -drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed, 1- -phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration Components
— Refrigeration
circuit
liquid- -line shutoff valve with sweat connections,
vapor- -line shutoff valve with sweat connections,
system charge of Puronr (R- -410A) refrigerant, and
compressor oil.
— Unit will be equipped with high- -pressure switch, low
pressure switch and filter drier for Puron refrigerant.
Operating Characteristics
— The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F/_C. The
power consumption at full load will not exceed _____
kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F/_C wet
bulb and _____ _F/_C dry bulb, and air entering the
unit at _____ _F/_C.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
91
CA16NA
1- -1/2 TO 5 NOMINAL TONS
components
will
include

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents