Machine Controls; Start-Stop Systems; Semi-Automatic Start-Stop; Full Automatic Start-Stop - Carrier 16JT Series Start Up & Operation Manual

60 hz double-effect hermetic absorption liquid chillers units 810-880, 080-150, 080l-150l
Table of Contents

Advertisement

MACHINE CONTROLS

Start-Stop Systems —
is selected by the customer. The most commonly used sys-
tems are described below. Review the descriptions and de-
termine which type applies to your system.
SEMI-AUTOMATIC START-STOP — In this basic system,
auxiliary equipment is wired into the machine control cir-
cuit and the machine is started and stopped manually with
the machine's Start and Stop buttons. Two variations are used:
With Pilot Relays — The coils for the chilled water and con-
densing water pump starters (or other auxiliary equipment)
are wired into the machine control circuit so that the aux-
iliary equipment operates whenever the machine operates.
The starter contacts and starter overloads remain in the ex-
ternal pump circuits. The flow interlocks for each pump are
also wired into the machine control circuit and must be closed
in order for the machine to operate.
With Manual Auxiliaries — With this system, the auxiliaries
must be started manually and independently from the ma-
chine start, and they must be operating before the ma-chine
can start. As with the pilot relay system above, the
1X1,2
Start-Stop Relays
1Y1,2
Shutdown Dilution Relays
2X
Run Relay
2T1
Time Delay Relay, Chilled Water Flow
3-1
Manual Start Switch Button
3-5
Manual Stop Switch Button
3-BZ
Alarm Buzzer Stop Button
3-VP
Manual Vacuum Pump On-Off Buttons
3X
Auto Start Relay
4X
Safety Device Relay
4Y
Safety Interlock Relay
20RV
Cycle-Guard™ Valve
23C
Low Load Limit Switch
26CW —
Low Chilled Water Temperature Limit
26GH
Generator Solution High-Temperature Limit
26MX
Hermetic Pump Fault Relay
26RP
Refrigerant Pump Motor High-Temperature LImit
26SH
Absorber Solution High-Temperature Limit
26SP1 —
Solution Pump No. 1 Motor High-Temperature Limit
26SP2 —
Solution Pump No. 2 Motor High-Temperature Limit
26SSP —
Solution Spray Pump Motor High-Temperature LImit
30X1,2 —
Safety Stop Interlock Relays
33RD
Refrigerant Dilution Level Switch
33RH
Refrigerant High-Level Switch
33RHX —
Refrigerant High-Level Relay
33RL
Refrigerant Low-Level Switch
33RM
Refrigerant Mid-Level Switch
33RMX —
Dilution Level Control Relay
33W
Generator Level Control Relay
43R
Remote-Local Switch
43RV
Cycle-Guard Auto.-Manual Selector Switch
51CP
Condensing Water Pump Overload
51CT
Cooling Tower Fan Overload
51EP
Chilled Water Pump Overload
51RP
Refrigerant Pump Overload Relay
51SP-1 —
Solution Pump No. 1 Overload Relay
51SP-2 —
Solution Pump No. 2 Overload Relay (Larger Sizes Only)
51SSP —
Solution Spray Pump Overload Relay (Some Larger Chillers)
51VP
Vacuum Pump Overload Relay (Optional)
62T1
Time Delay Relay, Shutdown Dilution
62T2
Time Delay Relay, Refrigerant Pump Start-Stop
62T3
Time Delay Relay, Capacity Control Soft Start
62T6
Time Delay Relay, Solution Pump Start-Stop
63GH
Generator High-Pressure Limit
63GX
Generator Fault Relay
69CW —
Low-Chilled Water Flow Switch
88EP
Chilled Water Pump Starter
88CP
Condensing Water Pump Starter
88CT
Cooling Tower Fan Starter
88RP
Refrigerant Pump Starter
88SP-1 —
Solution Pump No. 1 Starter
88SP-2
— Solution Pump No. 2 Starter (Larger Chillers Only)
88SSP
— Solution Spray Pump Starter (Some Larger Chillers)
1. The following items are not by Carrier:
• Chilled water pump, condensing water pump starters and discon-
nects
• Rigid or flexible conduit and junction boxes for wire and piping;
coded, except as noted
2. Solution and refrigerant pump starters are across-the-line definite
purpose type.
The type of start-stop system
LEGEND FOR FIGURES 10 AND 11
NOTES FOR FIG. 10
flow interlocks are in the machine control circuit and must
be closed for the machine to operate.
FULL AUTOMATIC START-STOP — This system is ba-
sically the same as the semi-automatic system with pilot re-
lays described above. Machine and auxiliary start and stop,
however, are controlled by a field-supplied thermostat, timer,
or other automatic device, and the machine Start and Stop
manual switch and indicator lights remain in the START mode.
As with all the Start-Stop systems, the machine's Start but-
ton must be depressed and released on initial start, and after
power interruption. After an abnormal shutdown, the Stop
button must be depressed to reset the circuit and silence the
alarm buzzer before depressing Start.
Control Wiring —
schematics and component identification.
NOTE: These schematics do not show all the options or varia-
tions that are available.
Control Panel —
troller, switches, pilot lights, and relays that operate the ma-
chine (Fig. 12 and 13).
88VP — Vacuum Pump Starter (Optional)
ABS — Absorber Pressure Switch
ABSX — Absorber Pressure Switch Relay
BZ
— Alarm Buzzer
BZX
— Alarm Buzzer Relay
CWX — Low Water Flow or Temperature Fault Relay
HM
— Hour Meter
LIX
— Load Limiter Relay
MCB — Main Circuit Breaker
RTD
— Temperature Sensor
RY1
— Auxiliary System Run Relay
T1,T2 — Water Pump Time Delay Relay
TIC
— Temperature Indicating Capacity Controller
TR
— Transformer
Z
— Surge Suppressor
Terminals on Control Panel Terminal Strip
Component Connection (Unmarked)
Component Connection (Marked)
External Terminal
GL
— Run Light
OL1 — Low Water Flow or Temperature Alarm Light
OL2 — Hermetic Pump Fault Alarm Light
OL3 — Generator Fault Alarm Light
OL4 — Vacuum Pump Fault Alarm Light
RL
— Stop Light
WL1 — Shutdown Dilution On Light
WL2 — High-Refrigerant Level Light
3. Solution and refrigerant pump motors are hermetic, 3-phase and op-
erate ±10% of rated voltage.
Rated Voltage
200/220
400/440
575
4. Controls are for 1-phase, 60 Hz, 110 v. The maximum permissible
current rating which all holding relays have is 12 amps inrush,
3 amps continuous, and 0.8 amps interruption. Make sure that the
wiring does not exceed above values.
10
See Fig. 10 and 11 for typical wiring
The control panel includes the con-
Hz (Cycle)
60
60
60

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents