LONG LINE APPLICATIONS

An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable
refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line
depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)
Liquid Line Size
No accessories needed within allowed
1/4
lengths
5/16
3/8
Note: See Long Line Guideline for details

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
Vapor Line Sizing and Cooling Capacity Losses — Puronr Refrigerant 2- -Stage Air Conditioner Applications
Maximum
Unit
Vapor Line
Liquid
Nominal
Diameters
Line
Size (Btuh)
(In.) OD
Diameters
(In. OD)
024
5/8
2--- Stage
3/8
Puron
3/4
AC
036
5/8
2--- Stage
3/8
3/4
Puron
AC
7/8
048
3/4
2--- Stage
3/8
7/8
Puron
AC
1 ---1/8
060
3/4
2--- Stage
3/8
7/8
Puron
1 ---1/8
AC
Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.
— Applications in this area are not recommended due to insufficient oil return

PHYSICAL DATA

Model
Unit Size --- Series
Operating Weight lb (kg)
Shipping Weight lb (kg)
Compressor Type
REFRIGERANT
Control
Charge lb (kg)
COND FAN
Air Discharge
Air Qty (CFM)
Motor HP
Motor RPM
COND COIL
Face Area (Sq ft)
Fins per In.
Rows
Circuits
VALVE CONNECT. (In. ID)
Vapor
Liquid
REFRIGERANT TUBES (In. OD)
Rated Vapor*
Liquid
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Beyond these lengths, long line accessories are required
Units On Same Level
120 (36.6)
80 (24.4)
26--- 50
51--- 80
81--- 100
(7.9--- 15.2)
(15.5--- 24.4)
(24.7--- 30.5)
0
1
1
0
0
0
1
2
4
0
0
1
0
0
0
1
2
2
0
1
1
0
0
1
2
4
0
1
2
0
0
0
024--- A
222 (101)
261 (118)
6.63 (3.01)
3100
1/10
800
21.56
25
1
4
3/4
3/4
Outdoor Below Indoor
No accessories needed within allowed
lengths
50 (15.2) vertical or 120 (36.6) total
35 (10.7) vertical or 80 24.4) total
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
101--- 125
126--- 150
151--- 175
(30.8--- 38.1)
(38.4--- 45.7)
(46.0--- 50.3)
2
3
3
0
1
1
5
6
7
1
2
2
0
1
1
3
4
5
2
2
2
5
6
7
2
3
4
1
1
1
187BNA
036--- A
048--- A
224 (102)
324 (147)
263 (119)
381 (173)
2 ---Stage Scroll
Puron (R---410A)
TXV (Puron Hard Shutoff)
6.88 (3.12)
11.63 (5.27)
Propeller Type, Direct Drive
Vertical
3400
4300
1/5
1/4
800
800
21.56
25.15
25
20
1
2
4
7
7/8
7/8
3/8
7/8
1 ---1/8
3/8
4
Outdoor Above Indoor
175 (53.3)
120 (36.6)
80 (24.4)
176--- 200
201--- 225
226--- 250
(53.6--- 60.0)
(61.3--- 68.6)
(68.9--- 76.2)
4
4
5
1
1
1
9
10
11
3
3
4
1
1
2
6
7
7
3
3
3
9
10
11
4
5
5
1
1
1
180BNA
060--- A
036--- A
334 (152)
306 (139)
391 (177)
372 (169)
15.13 (6.86)
13.37 (6.06)
4450
3100 / 3600
1/4
1/5
800
582 / 690
30.18
25.15
20
20
2
2
8
7
7/8
7/8
3/8
1 ---1/8
7/8
3/8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Evolution 180b

Table of Contents