Installation Space - Toshiba Carrier MMD-AP0074SPH2UL Installation Manual

Air conditioner multi type
Hide thumbs Also See for Carrier MMD-AP0074SPH2UL:
Table of Contents

Advertisement

Available languages

Available languages

Installation space

Reserve sufficient space required for installation or service work.
The indoor unit does not have a built-in air filter.
The type of air filters required will be specified by applicable codes and requirements for the indoor unit installation.
All filters are locally procured.
Always install the air filter (Local procure) in a location that permits easy maintenance, such as behind the intake
grille. (If no air filter is installed, dust will collect in the heat exchanger, which may cause the air conditioner to fail
or to leak.)
CAUTION
Leave sufficient space to remove the air filter when you attach it.
Air discharge
3.9" (100) or more
<Under air intake>
Ceiling
<Back air intake>
Ceiling
7-EN
Unit: in (mm)
0.2" (5) or more
8.3" (210)
15.8" (400) or
more
0.2" (5) or
more
8.3" (210)
11.2" (285) or more
Air intake
3.9" (100) or more
0.2" (5) or more
8.3"
9.3" (235) or
Air intake
(210)
more
11.8" (300) or more
Service space
Reserve sufficient space required for installation or service work.
Air discharge
2" (50)
Ceiling
39.2" (995)
Ceiling opening size
39.2" (995)
Filter cleaning sign term setting
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote control can be changed
according to the condition of installation.
For setup method, refer to "Filter sign setting" in the Applicable controls of this Manual.
– 4 –
3.9" (100)
29.3" (745)
29.3" (745)
Unit: in (mm)
EN
8-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents