SYSTEM CONTROL

1. VARIETY OF SYSTEM CONTROL FUNCTIONS
1 Group control with
a single remote
controller
(See page 64.)
2 Both remote
ON/OFF and indi-
vidual controls
(See page 65.)
w Timer adapter
(PAC-SA89TA-E)
is needed.
3 Individual control
by grouping
remote controllers
(See page 66.)
4 Multiple remote
control display
(See page 67.)
w Multiple display
adapter
(PAC-SA88HA-E)
is needed.
5 Auto restart
function
(See page 67.)
Unit
Unit
Remote
controller
Optional
adapter
Remote
Remote
ON/OFF
controller
switch
Unit
Unit
Remote
controller
Unit
Unit
Remote controll
Remote
display board
controller
Circuit breaker
Remote
controller
Many units, installed at different locations, can be started
and controlled with a angle remote controller. The remote
controller can be mounted in a different location using a
non-polar two-wire cable, which can be extended up to
Unit
500m. A maximum of 50 units can be controlled with a
single remote controller. All units operate in the same
mode.
All units can be turned on or off simultaneously using a
remote ON-OFF switch. Also, each unit can be controlled
Relay box
individually by each remote controller. Dunning remote
ON-OFF control, a message of "CENTRALLY CON-
TROLLED" is displayed on the LCD of the remote con-
Unit
troller.
This is available for both one unit control and several units
control.
By grouping the remote controllers in one place, several
units installed at different locations can be controlled indi-
vidually, and operation conditions of all units are visible
Unit
without a special control board. The control method is the
same as that of the single unit with a single remote con-
troller.
Several units can be controlled with a remote control dis-
play board. Operation conditions of all the units are visi-
ble with the remote control display board.
Individual control by each remote controller is also possi-
Unit
ble.
A unit can be started or stopped with the circuit breaker
on or off.
Remote controller is also available.
With this function, when the power is restored after power
failure, the unit will restart automatically. (However, when
the remote controller POWER ON/OFF button is OFF, the
unit will not start.)