The water heater has a high-temperature shutoff switch built in as a standard safety feature (called a
Hi-Limit switch) therefore a "pressure only" relief valve is required
• This water heater does not come with an approved pressure relief valve
• An approved pressure relief valve must be installed on the hot water outlet
• The pressure relief valve must conform to ANSI Z21.22 or CAN 1-4.4 and installation must follow local
codes
• The discharge capacity must be at least 120,000 BTU/h for the 140 (T-H3M) models
• The pressure relief valve needs to be rated for a maximum of 150 psi (1 MPa)
• The discharge piping for the pressure relief valve must be directed so that the hot water cannot splash
on anyone or on nearby equipment Follow local codes
• Attach the discharge tube to the pressure relief valve and run the end of the tube to within 6 inches
(152 mm) from the floor This discharge tube must allow free and complete drainage without any
restrictions
• If the pressure relief valve installed on the water heater discharges periodically, this may be due to a
defective thermal expansion tank, defective pressure relief valve, or it could be signs of internal scale
build up
• The pressure relief valve must be manually operated periodically to check for correct operation
• No valves may be placed between the relief valve and the water heater
• The water heater does not include a built-in condensate neutralizer cartridge for reducing the pH level
of condensate water If local codes dictate that condensate must be neutralized prior to drainage, a
condensate neutralizer must be installed An accessory Neutralizer assembly is sold separately
• In the absence of applicable local codes and regulations, the manufacturer recommends that
condensate be disposed of into a standard drain Connect a drain tube from the condensate drain port
(shown below) located on the bottom of the water heater to a standard drain
Follow all code requirements
of the local authority on
condensate neutralizers and
whether or not they are required
for the installation
-Pressure relief valve-

CONDENSATE DRAIN

Condensate drain port
23
Page
Installation Manual
Installation

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T-h3m-os

Table of Contents