SM Series Heat Pump
14. Reinstall blower motor and inlet ring assembly
by reversing Step #6. (Figure #61)
Figure # 61
15. Reconnect blower motor electrical plug and
ground wire.
16. Reinstall diagonal bracket(s). (Figure #62)
Figure # 62
SM Series Heat Pump
Condensate Drain Connection Re-
configuration
When re-configuring the unit from Left-Hand
Return to Right-Hand Return it is necessary to
relocate condensate drain connection from FRONT
left corner post to BACK left corner
post.(Figure#63)
Figure # 63
1. Cut the condensate drain hose on the inside of
cabinet.
Ensure to retain the spring
2. Remove and retain condensate drain plastic
fitting and grommet from the hose by pulling it
away from the hose (barb style connection).
(Figure#64)
Figure # 64
Vertical configurability | 19
6 720 220 406 (2013/1)