Mitsubishi Electric PUHZ-P100VHA.UK Service Manual page 82

Split-type, heat pump air conditioners outdoor unit
Table of Contents

Advertisement

Request content
Error history 1 (latest)
103
104
Error history 2 (second to last)
Error history 3 (third to last)
105
Abnormal thermistor display
106
(TH3/TH6/TH7/TH8)
107
Operation mode at time of error
Compressor-Operating current at time of error
108
109
Compressor-Accumulated operating time at time of error
110
Compressor-Number of operation times at time of error
Discharge temperature at time of error
111
112
Outdoor unit - Liquid pipe 1 temperature (TH3) at time of error
113
Outdoor unit - Liquid pipe 2 temperature at time of error
114
Outdoor unit-2-phase pipe temperature (TH6) at time of error
115
116
Outdoor unit-Outside air temperature (TH7) at time of error
117
Outdoor unit-Heat sink temperature (TH8) at time of error
Discharge super heat (SHd) at time of error
118
119
Sub-cool (SC) at time of error
120
Compressor-Operating frequency at time of error
Outdoor unit at time of error
121
• Fan output step
Outdoor unit at time of error
122
• Fan 1 speed (Only for air conditioners with DC fan)
Outdoor unit at time of error
123
• Fan 2 speed (Only for air conditioners with DC fan)
124
LEV (A) opening at time of error
125
126
LEV (B) opening at time of error
127
128
129
130
Thermostat ON time until operation stops due to error
131
Indoor - Liquid pipe temperature at time of error
132
Indoor-2-phase pipe temperature at time of error
133
Indoor at time of error
134
• Intake air temperature <Thermostat judge temperature>
135
136
137
138
139
140
~
146
147
148
149
150
Indoor-Actual intake air temperature
Indoor - Liquid pipe temperature
151
152
Indoor-2-phase pipe temperature
Description
(Display range)
Displays error history. (" - - " is displayed if no history is present.)
Displays error history. (" - - " is displayed if no history is present.)
Displays error history. (" - - " is displayed if no history is present.)
3
: TH3
6 : TH6
7 : TH7
8 : TH8
0 : No thermistor error
Displayed in the same way as request code "0".
0 – 50
0 – 9999
0 – 9999
3 – 217
-40 – 90
-40 – 90
-39 – 88
-39 – 88
-40 – 200
0 – 255
0 – 130
0 – 255
0 – 10
0 – 9999
0 – 9999
0 – 500
0 – 500
0 – 999
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
82
Unit
Remarks
Code
Code
Code
Sensor
number
A
10 hours
100 times
:
:
:
:
:
:
:
:
Hz
Step
rpm
"0" is displayed if the air conditioner is a single-
rpm
fan type.
Pulses
Pulses
Minutes
Average value of all indoor units is displayed if the air condi-
:
tioner consists of two or more indoor units (twin, triple, quad).
Average value of all indoor units is displayed if the air condi-
:
tioner consists of two or more indoor units (twin, triple, quad).
:
:
:
:

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents