SW2 setting
Indoor setting temperature
ON
17~30
1
2 3 4 5 6
Outdoor pipe temperature / Cond./
Eva. (TH6)
ON
-39~88
1
2 3 4 5 6
Outdoor outside temperature (TH7)
-39~88
ON
1
2 3 4 5 6
Outdoor heat sink temperature (TH8)
-40~200
ON
1
2 3 4 5 6
Discharge super heat. SHd
0~255
ON
Cooling = TH4-TH6
1
2 3 4 5 6
Heating = TH4-TH5
Sub cool. SC
0~130
ON
Cooling = TH6-TH3
1
2 3 4 5 6
Heating = TH5-TH4
Input current of outdoor unit
ON
1
2 3 4 5 6
Targeted operation frequency
0~255
ON
1
2 3 4 5 6
DC bus voltage
180~370
ON
1
2 3 4 5 6
Display detail
Explanation for display
17~30
-39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
-39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
-40~200
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
(When the thermistor detects 100: or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0~255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
180~370
(When it is 100V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
66
Unit
:
:
:
:
°C
°C
0.1 A
Hz
V