Mitsubishi Electric PUHZ-P100VHA.UK Service Manual page 48

Split-type, heat pump air conditioners outdoor unit
Table of Contents

Advertisement

10-6. HOW TO CHECK THE PARTS
PUHZ-P100VHA.UK PUHZ-P125VHA.UK PUHZ-P140VHA.UK
Parts name
Thermistor (TH3)
Disconnect the connector then measure the resistance using a tester.
<Outdoor pipe>
(Surrounding temperature 10:~30:)
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Thermistor (TH8)
<Heat sink>
Fan motor(MF1,MF2)
Refer to next page.
Solenoid valve coil
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
<Four-way valve>
(21S4)
Motor for compressor
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
U
(MC)
V
W
Linear expansion valve
Disconnect the connector then measure the resistance using a tester.
(LEV-A)
(Winding temperature 20:)
Gray
M
1
2
Orange
3
Red
4
Yellow
5
Black
6
Measure the resistance between the terminals using a tester.
Solenoid valve coil
(Surrounding temperature 20:)
<Bypass valve>
(SV)
For P100
Normal
TH4
160k"~410k"
TH3
TH6
4.3k"~9.6k"
TH7
TH8
39k"~105k"
P100
1500±150"
P100
0.88"
Gray - Black
Gray - Red
Normal
1450±150"
Check points
Abnormal
Open or short
Normal
P125,P140
1435±150"
Normal
P125,P140
0.266"
Normal
Gray - Yellow
Gray - Orange
46±3"
Abnormal
Open or short
48
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents