Section 3-3-1: Venting Layout; Top Vent, Wall Mounted Graph, L52Df; Top Vent, Wall Mounted Termination (One Elbow) - Montigo L52DF Installation & Maintenance Manual

L series residential fireplace
Table of Contents

Advertisement

The Venting graph: L52DF*
Measure the vertical height from the fireplace hearth to the centre of the
termination and the horizontal run from the fireplace flue collar to the wall
flange of the termination. Plot on the Venting Graph Figure 14 with an 'X'.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 84" and the horizontal run to
the wall flange of the vent termination is 36", this would be an acceptable
installation.
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 108" and the horizontal run to
the wall flange of the vent termination is 120", this would be an acceptable
installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 48" and the
horizontal run to the wall flange of the vent termination is 108", this would
nOT be an acceptable installation.
A
Figure 11. L52DF Top Vent Venting Graph
nOTES:
All dimension lengths for vertical or horizontal runs are
measured from centre of the vent pipe.
Venting runs must fall within the limits set by the venting
graph (see Figure 11).
Available Top Vent Components
The following venting components are available for the L52DF Top Vent:
5" / 8" Venting
A - Termination
PTO-3 (3" Length)
PTO-3F (3" Length)
B - Stucco Kits
MSR (Stucco Frame)
MOSR (Stucco Can)
BSR ( Brick Can)
C - Flex Sections
PFL-1 (12" Section)
PFL-2 (24" Section)
PFL-3 (36" Section)
PFL-4 (48" Section)
D - Rigid
PEXT-1 (12" m/f Section)
Sections
PEXT-2 (24" m/f Section)
PEXT-3 (36" m/f Section)
PEXT-4 (48" m/f Section)
E - Elbows
PEL-90MM (m/m 90° Elbow)
PEL-90FF (f/f 90° Elbow)
PEL-90FM (f/m 90° Elbow)
XG0185 - 050611
Installation
B
C
Power Vent models, LDVPV47
EDVRSPV58, and EDVWSPV58
to be used within the shaded area of
graph. (See Index of this guide for
applicable Product page).
Power Vent models, LDVPV47
EDVRSPV58, and EDVWSPV58
to be used within the shaded area of
graph. (See Index of this guide for
applicable Product page).
E - Elbows
PEL-90MM (m/m 90° Elbow)
PEL-90FF (f/f 90° Elbow)
PEL-90FM (f/m 90° Elbow)
Example 1:
For our shortest venting configuration use components A and E (see
Figure 11a).
Figure 11a. Typical Top Vent installation. If the 90° elbow is installed directly
on the fireplace, for height to the center of the termination.
Important:
An inspection of the explosion relief flappers and door must be
made prior to lighting the fireplace. This will ensure the door gas-
keting material will provide an adequate seal during operation.
Horizontal Venting
PEXT Section
Figure 11b. Typical Top Vent installation. The solid sections can be used in
various combinations to obtain the desired vent run. The vent run must fall within
the limits set by the venting graph.
L52DF* Indoor Gas Fireplace
RHS101
PEL
90° Elbow
Termination
Page 11