If  a  third  Cygnus  is  being  used,  connect  another  data  cable  between  D2  (Fig.  1,  D1)  of  Cygnus  2  and  D1  (Fig.  1,  D2)  
of  Cygnus  3  by  removing  the  corresponding  protec ve  covers  and  screwing  in  the  retaining  rings.
7.
Run  a  16A  CEEform  extension  cable  from  the  AC  output  (Fig.  1,  E2)  of  each  Cygnus  into  the  corresponding  num-­‐
bered  inlet  of  the  parallel  junc on  box.
8.
Run  a  32A  cable  from  output  connector  of  the  junc on  box  to  your  designated  power  distribu on  unit  or  directly  
to  your  consumer(s).
9.
Switch  on  the  RCDs  and  MCBs  (Fig.  1,  B1  &  B2)  on  all  units.
10.
Turn  on  Cygnus  1  using  the  Power  On/Off  Switch  (Fig.  1,  C4).  You  will  hear  a  long  'beep'  and  the  panel  backlight  
will  illuminate.  Cygnus  1  should  be  le  in  Standby  Mode  at  this  point.
11.
Turn  on  the  Power  On/Off    Switch  (Fig.  1,  C4)  on  Cygnus  2  and  if  used,  Cygnus  3  so  that  all  3  are  in  Standby  
Mode.
12.
On  the  RCC-03  (Fig.  1,  C2)  of  Cygnus  1.  Press  Up,  then  Down  to  access  the  Parallel  display.
13.
Turn  on  Cygnus  1  using  its  RCC-03  (Fig.  1,  C2).  All  connected  units  should  turn  on  simultaneously.
14.
Ensure  all  junc on  box  red  indicators  are  illuminated.  This  shows  that  all  units  are  on  and  opera ng  in  parallel  
mode.  Check  that  all  the  RCDs  and  MCBs  (Fig.  1,  B1  &  B2)  are  s ll  in  the  'On'  posi on  and  none  of  them  have  
tripped  out.
4.3  Connec ng  in  Series
1.
Three  units  must  be  used.    
2.
To  check  whether  the  units  are  configured  correctly  for  three  phase  opera on,  check  the  RCC-03  Cygnus  number
(Fig.  4,  F2).  The  first  unit  should  display  L1,  the  second  L2  and  the  third  L3.  Do  not  a empt  to  connect  the  units  
in  series  if  this  is  not  the  case.  
3.
Once  the  unit  numbers  have  been  determined,  posi on  the  three  units  with  L1  on  the  le ,  L2  in  the  centre  and  
L3  on  the  right.
4.
Turn  off  the  power  on  all  units  using  the  Power  On/Off  switch  (Fig.  1,  C4).
5.
Cygnus  1  and  Cygnus  2  should  be  set  as  Open  (Fig.  1,  C3:  rotate  switch  an -clockwise)  and  Cygnus  3  as  Terminat-­‐
ed  (Fig.  1,  C3:  rotate  switch  clockwise).
6.
Star ng  with  unit  L1,  connect  the  first  data  interlink  cable  to  D2  (Fig.  1,  D2)  on  the  control  panel.  Ensure  that  as  
the  connectors  are  plugged  in,  the  connector's  retaining  ring  is  screwed  clockwise  in  to  the  receptacle  on  the  
panel  connector.  This  ensures  that  water  integrity  is  maintained.
7.
Connect  the  other  end  of  this  cable  to  D1  (Fig.  1,  D1)  on  the  control  panel  of  unit  L2.  
8.
Plug  a  second  Data  cable  into  D2  (Fig.  1,  D2)  on  the  control  panel  of  the  unit  L2.
9.
Connect  the  other  end  of  this  cable  to  D1  (Fig.  1,  D1)  on  the  control  panel  of  unit  L3.
10.
Run  a  16A  cable  from  the  AC  output  (Fig.  1,  E2)  of  each  Cygnus  into  the  corresponding  numbered  input  of  the  
series  junc on  box.
11.
Run  a  32A  3  phase  (3P+N+E)  CEEform  cable  from  the  output  connector  of  the  junc on  box  to  your  designated  
power  distribu on  unit  or  consumer(s).
12.
Check  that  all  the  data  cable  connec ons  are  plugged  in  correctly.
13.
Switch  on  the  RCDs  and  MCBs  (Fig.  1,  B1  &  B2)  on  all  units.
14.
Double  check  that  all  connec ons  are  secure,  then  turn  on  unit  1  using  the  Power  On/Off  Switch  (Fig.  1,  C4).  A  
long  'beep'  will  be  audible  and  the  RCC-03  backlight  will  illuminate.  Unit  1  should  be  le  in  standby  mode  at  this  
point.
15.
Turn  on  the  Power  On/Off    Switch  (Fig.  1,  C4)  on  Cygnus  2  and  then  Cygnus  3  so  that  all  three  are  in  standby  
mode.