4. Connec ng  Mul ple  Cygnus  Portable  Solar  Generators
4.1  Introduc on
It  is  possible  to  connect  mul ple  Cygnus  units  together  using  RJ45  data  interlink  cables  and  AC  junc on  boxes.  There  are  two  
possible  configura ons:
Cygnus  in  Parallel
Either  two  or  three  units  can  be  connected  in  parallel.  In  each  case  doubling  or  tripling  the  peak  output  and  ba ery  bank  ca-­‐
pacity  whilst  maintaining  a  single  phase  230V  AC  output.
Connec ng  three  Cygnus  units  in  parallel  will  mul ply  the  run- me  approximately  three   mes  compared  with  using  a  single  
Cygnus  with  the  same  load.  Connec ng  mul ple  units  will  mul ply  the  current  available  at  the  output.  For  example:  connec ng  
2  CYG500/1380/24  units  with  a  peak  capacity  of  5.0kVA  provides  a  total  system  output  of  10.0kVA.
Cygnus  in  Series  (3  Phase)
Units  can  be  connected  in  series  to  provide  a  415V  three  phase  output.  This  requires  that  three  units  are  connected  
together  using  a  junc on  box  (available  separately  from  the  manufacturer).
Parallel  and  series  junc on  boxes  are  only  to  be  used  for  their  specific  role  and  are  not  
interchangeable.
Check  with  the  manufacturer  that  the  units  are  preconfigured  for  parallel  or  series  use  before  
a emp ng  connec on.
It  is  important  that  the  D1,  D2  &  D3  data  connec ons  (Fig.4,  D1-3)  always  have  the  caps  or  cable  re-­‐
taining  rings  secured.  Failure  to  follow  this  procedure  will  cause  water  ingress  damage  and  invalidate  
the  warranty.
Units  which  do  not  have  the  same  model  number  prefix  are  not  suitable  for  series  or  parallel  connec-­‐
on.  For  example:  It  is  possible  to  connect  two  or  three  CYG5000/----/--  and  it  is  not  possible  to  con-­‐
nect  one  CYG5000/----/--  to  one  CYG3500/----/--.
When  connec ng  in  series  or  parallel,  the  so ware  version  of  every  unit  must  be  the  same.  Otherwise  
the  units  may  not  start.
Only  use  data  cables  supplied  by  the  manufacturer.
Any  interrup on  of  the  data  connec on  will  cause  all  units  to  power  off.
4.2
Connec ng  in  Parallel
A  parallel  junc on  box  (available  separately  from  the  manufacturer)  is  required  to  connect  the  AC  outputs  of  each  unit.  
1.
Either  two  or  three  units  may  be  used.
2.
Turn  off  the  power  on  all  units  using  the  Power  On/Off  switch  (Fig.  1,  C4).
3.
If  using  two  units,  Cygnus  1  should  be  set  as  open  (Fig.  1,  C3:  rotate  switch  an -clockwise)  and  Cygnus  2  as  Termi-­‐
nated  (Fig.  1,  C3:  rotate  switch  clockwise).
4.
If  using  three  units,  Cygnus  1  and  Cygnus  2  should  be  set  as  Open  (Fig.  1,  C3:  rotate  switch  an -clockwise)  and  
Cygnus  3  as  Terminated  (Fig.  1,  C3:  rotate  switch  clockwise).
5.
Star ng  with  Cygnus  1,  unscrew  the  protec ve  cover  from  D2  (Fig.  1,  D2)  on  the  control  panel  and  connect  the  
first  data  interlink  cable.  Ensure  that  as  the  connector  is  plugged  in,  the  connector's  retaining  ring  is  screwed  
clockwise  in  to  the  receptacle  on  the  panel  connector.  This  ensures  that  water  integrity  is  maintained.
Cygnus  User  Manual  -    v3.0            2011  