Honeywell STT850 SMARTLINE User Manual page 40

Temperature transmitter
Hide thumbs Also See for STT850 SMARTLINE:
Table of Contents

Advertisement

Excess Delta
Delta Limit
Bumpless
Damping
Hysteresis
Break Detect
Latching
CJ Source
Fixed CJ Value
Page 30
the Loop
Enable, Disable
Value that will
produce a
Diagnostic if
exceeded by
Sensor Delta.
Damping value for
the transition of
Loop Control
between Sensors
when Loop Ctrl
Mode is Split-
Range or
Redundant
Hysteresis value
relative to the MRV
for the transition of
Loop Control
between Sensors
when Loop Ctrl
Mode is Split-
Range
Enable, Disable
When enabled,
causes all Critical
Diagnostics to latch
to the Fault state,
and will not be
released until a
power cycle occurs.
Internal, External,
Fixed
When CJ Source is
Fixed, specifies the
Cold Junction
temperature value
for thermocouple
Sensor types.
STT850 Temperature Transmitter User's Manual
Enable or disable Critical
Diagnostic when Sensor
Delta (difference between
Sensor 1 and Sensor 2)
exceeds Delta Limit. A Non-
Critical Diagnostic occurs if
Disabled.
When enabled, adds a
constant bias value to the
Sensor 2 measured value to
equate it to the Sensor 1
measured value at the
moment selected.
Determines the source of the
Cold Junction compensation
for thermocouple Sensor
types.
Revision 1