Mitsubishi Electric MSZ-GC22VA Service Manual page 11

Split-type, heat pump air conditioners
Hide thumbs Also See for MSZ-GC22VA:
Table of Contents

Advertisement

NOTE 2
FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won't operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect
indoor units beyond the outdoor unit capacity.
Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and
the others for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor
units cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the
same operation mode.
•When indoor unit starts the operation while the defrosting of outdoor unit is being done, it takes a few
minutes(max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant
flowng may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
9-5. AUTO VANE OPERATION
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.
(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the selected
angle.
Confirming of standard position is performed in the following cases:
(a) When the operation starts or finishes (including timer operation).
(b) When the test run starts.
(c) When standby mode (only during multi system operation) starts or finishes.
(4) VANE AUTO (
) mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle to make the optimum room temper-
ature distribution.
In COOL and DRY operation
In HEAT operation
(5) STOP (operation OFF) and ON TIMER standby
In the following cases, the horizontal vane returns to the closed position.
(a) When OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When ON TIMER is ON standby.
(6) Dew prevention
During COOL or DRY operation with the vane angle at Angle 2 ~ 4 when the compressor cumulative operation time
exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
OPERATION INDICATOR
Horizontal
position
11
Lighted
Blinking
Not lighted
Vane angle is fixed to Horizontal position.
Vane angle is fixed to Angle 4.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents