Fine Adjustment Of Signal Output - Optex SC-T4 Instruction Manual

Hide thumbs Also See for SC-T4:
Table of Contents

Advertisement

4
Press
to terminate the Signal Output Range Low Limit
Setting.
CAUTION:
When Err6 is displayed, the value is out of the setting range.
(2) Signal Output High Limit Setting
1
Press
and select the
High
Limit.
"-Hi-" and "the setting value" comes on
alternatively.
2
Press
for 2 seconds or more, the
Signal Output High Limit value is
displayed.
3
Enter "300" on the Display.
Reference
Move the digit to be entered using the right and left arrow buttons
( 1 digit
10 digit
At this time, the selected digit blinks.
Enter a numerical value ( 0, 1, 2, ..., 9 ) into the selected digit using the
upper and lower arrow buttons
value and
button decreases the value.
While pressing
changed.
To cancel the Signal Output High Limit Setting, press
To change the Display for the Measurements Indication mode, press
again.
4
Press
to terminate the Signal Output Range High
Limit Setting.
CAUTION:
When Err6 is displayed, the value is out of the setting range.
Signal Output
100 digit
100 digit ) .
.
button increases a numeric
buttons, the values displayed are continuously
.
6

Fine Adjustment of Signal Output

Fine Adjustment of Lower Limit 4mA and Upper Limit 20mA of Signal
Output (4-20mA) can be made.
CAUTION:
First make the Fine Adjustment of Lower Limit 4mA, and then make the Fine
Adjustment of Upper Limit 20mA.
Otherwise the value of the Upper Limit 20mA cannot be adjusted accurately.
Pip
1
Fine Adjustment of Lower Limit 4mA
1
Simultaneously press both right and left
arrow buttons
At this time, "-4-" is indicated in the Display.
Pip Pip
And, "ZERO" blinks and "SPAN" comes on.
2
While making sure of the values displayed by the
connecting equipment such as recorder, make the Fine
Adjustments of the Lower Limit 4mA with the up and down
arrow buttons
4
Press
Limit 4mA.
CAUTION:
When both right and left arrow buttons
Output of 4mA will be produced irrespectively of the measurement value.
Reference
To cancel the Fine Adjustment of the Lower Limit 4mA, press
.
.
to terminate the Fine Adjustments of the Lower
are pressed simultaneously, Signal
.